| 2012-10-15 13:18:38 | 7501 NORTH JOG ROAD | | | PERMIT #12100386 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET. | | | NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT | | | LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL | | | CONTRAST THE BACKGROUND. | | | | | | THERE DOES NOT APPEAR TO BE ANY FIRE HYDRANTS LOCATED | | | WITHIN THE FENCED AREA CONTAINING ALL THE CONSTRUCTION | | | TRAILERS, EQUIPMENT AND STAGING MATERIALS. | | | | | | PROVIDE STAIR AND HANDRAIL DETAILS FOR GAINING ACCESS | | | INTO THE TRAILERS. | | | | | | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | | | | THE TWO PROPOSED TRAILERS, AS WELL AS THE EXISTING 5 OR | | | 6 TRAILERS, DO NOT APPEAR TO HAVE ADEQUATE SPACING TO | | | PREVENT A MAJOR CONFLAGRATION AMONGST ALL TRAILERS. PER | | | NFPA 241 (STANDARD FOR SAFEGUARDING CONSTRUCTION, | | | ALTERATION, AND DEMOLITION OPERATIONS) | | | THE TRAILERS SHALL BE PROTECTED BY AN AUTOMATIC | | | SPRINKLER SYSTEM OR THE TRAILERS SHALL BE SPACED A | | | MINIMUM OF 50 FEET APART PER TABLE 4.2.1. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|