Plan Review Notes
Plan Review Notes For Permit 12100385
Permit Number 12100385
Review Stop B
Sequence Number 1
Notes
Date Text
2012-10-23 08:57:48****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE REPORT PROVIDED APPEARS TO BE PARTIAL REPORTS;
 FIRST PAGE IS FOR REPORT NGC 5004018 REFERENCING ASTM E
 90, BUT PAGE 2 IS FOR REPORT NGC 7004062, TEST ASTM E
 492-90. THE MANUFACTURER SPEC SHEET GIVES A RESULT OF
 72 (UNDERLAYMENT ONLY).
  
 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE REPORT PROVIDED APPEARS TO BE PARTIAL
 REPORTS; FIRST PAGE IS FOR REPORT NGC 5004018
 REFERENCING ASTM E 90, BUT PAGE 2 IS FOR REPORT NGC
 7004062, TEST ASTM E 492-90. THE MANUFACTURER SPEC
 SHEET GIVES A RESULT OF 68 (UNDERLAYMENT ONLY).
  
 3. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 4. VALUE TOO LOW; PROVIDE A VALUE WHICH INCLUDES ALL
 MATERIALS AND LABOR, FBC 109. CONTRACT OR RECEIPTS MAY
 BE REQUIRED.
  
  