| 2012-11-06 16:58:03 | 12100373 |
| | 1801 PALM BEACH LAKES |
| | FOUNDATION PERMIT |
| | |
| | THIS APPROVAL IS FOR FOUNDATION PERMITTING. PLEASE |
| | ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW COMMENTS |
| | PRIOR TO VERTICAL CONSTRUCTION. |
| | |
| | E 001 |
| | NOTE 45: UPDATE WIND LOAD REQUIREMENTS FOR LIGHT POLES |
| | FOR EXPOSURE CATEGORY AND IMPORTANCE FACTOR. FBC 2010 |
| | 1609, ASCE 7-10 |
| | |
| | NOTE 56: MULTI-WIRE BRANCH CIRCUITS REQUIRE A MEANS |
| | THAT WILL SIMULTANEOUSLY DISCONNECT ALL UNGROUNDED |
| | CONDUCTORS. NEC 210.4 |
| | |
| | E 201 |
| | INDICATE AND LABEL ON THE PLAN THE METHOD SELECTED TO |
| | PROVIDE THE REQUIRED SAFE WORKING CLEARANCES AND |
| | DEDICATED WORKING SPACE AT THE ELECTRICAL PANEL BOARDS. |
| | NEC 110.26, 240.24 |
| | |
| | E202, 205, ETC ? |
| | PROVIDE A DETAIL WHICH ESTABLISHES A COMMON BONDING |
| | CONDUCTOR FOR THE SEPARATELY DERIVED ELECTRICAL |
| | SYSTEMS. NEC 250.30 (A) (4) |
| | GROUNDING ELECTRODE TAPS SHALL BE PROPERLY SIZED AND |
| | CONNECTED WITH A LISTED CONNECTOR OR EXOTHERMIC WELDING |
| | PROCESS. NEC 250.30(A) (4) (A,B,C) |
| | |
| | E601 |
| | PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL |
| | DISCONNECTS AND FOR FLASH PROTECTION. NEC 110.22, |
| | 110.16 |
| | PROVIDE A DETAIL WITH DIMENSIONS SHOWING THE REQUIRED |
| | WORKING CLEARANCES AND DEDICATED WORKING SPACE WITHIN |
| | THE ELECTRICAL EQUIPMENT ROOMS. INDICATE ON THE FLOOR |
| | PLAN WITHIN EACH TENANT SPACE THE REQUIRED WORKING |
| | CLEARANCES. NEC 110.26, 240.24 |
| | |
| | E401, 402, 403 |
| | |
| | INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE |
| | NEW SERVICE AND SWITCH GEAR. NEC 110.9, 110.10 |
| | PANEL SCHEDULES AND MAIN DISCONNECTS ARE REQUIRED FOR |
| | TENANT SPACES. NEC 215.5 |
| | GROUND-FAULT PROTECTION IS REQUIRED FOR THE METERING |
| | SWITCH BOARDS. NEC 230.95 |
| | |
| | NOTES: |
| | SEPARATE PERMITS ARE REQUIRED FOR VOICE AND DATA, FIRE |
| | ALARM SYSTEMS AND LIGHTNING PROTECTION. |
| | |
| | |
| | ROBERT LECKY |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6718 |
| | |
| | |