| Plan Review Notes For Permit 12100361 |
| Permit Number |
12100361 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-10-29 13:59:04 | PLANS DENIED | | | 1) REFER TO SECTION 607.5.1 FIRE WALLS 2010 FBC (M) | | | MISSING | | | TWO FIRE DAMPERS ON 8X6 SUPPLY AND 10X10 RETURN DUCT. | | | 2) ALL NEW GRAILS AND DUCT MUST HAVE SIZE. PER SECTION | | | 107 FBC 2010 | | | 3) SEPARATE APPLICATION REQUIRED FOR WALK IN COOLERS , | | | FREEZERS | | | AND HOODS . | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] | | | |
|