| 2013-01-08 09:56:40 | BUILDING PLAN REVIEW |
| | PERMIT: 12100355 |
| | ADD: 825 SOUTHERN BLVD SUITE # 5 |
| | CONT: MTC REMODELING |
| | TEL: (561)655-5956 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 4TH REVIEW |
| | JAN. 08/2013 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. |
| | |
| | 2) 4TH REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS. |
| | THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE |
| | 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 3) 4TH REQUEST. 2010 FBC-B 1609.1.1 DETERMINATION OF |
| | WIND DESIGN- CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | 1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | |
| | 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 5) COMPONENTS & CLADDING PRESSURES POSITIVE & NEGATIVE |
| | TABLE 1609.2(2) . |
| | |
| | 4) COMPLIED. |
| | |
| | PLEASE TAKE NOTE!!!!!!!!!!!!!!!!! |
| | |
| | *****CHAPTER 553.80(2)(B) FLORIDA STATUTES *****STATES |
| | THAT A LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR |
| | TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE REJECTED |
| | THREE |
| | OR MORE TIMES FOR REPEATED FAILURE TO CORRECT A CODE |
| | VIOLATION. |
| | |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |