| 2012-11-05 09:37:15 | 12100355 | | | 823 SOUTHERN BLVD. | | | COMMERCIAL RENOVATION | | | | | | NONMETALLIC-SHEATHED CABLE (ROMEX) IS NOT AN ACCEPTABLE | | | WIRING METHOD FOR THIS OCCUPANCY. NEC 334.12 | | | ALL RECEPTACLES LOCATED WITH IN SIX FEET OF A SINK MUST | | | BE GFCI PROTECTED. NEC 210.8 | | | INCLUDE A RISER PLAN SHOWING THE NEW AND EXISTING | | | ELECTRIC SERVICE COMPONENTS WITH MAIN DISCONNECT, | | | SERVICE GROUNDING, AND LOCATION. NEC 110.26, 215.5 | | | PROVIDE A LIGHTING DENSITY CALCULATION SHOWING | | | COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE | | | REQUIREMENTS. FBC ENERGY CONSERVATION 505.3 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|