| 2012-11-07 11:23:58 | BUILDING PLAN REVIEW |
| | PERMIT: 12100295 |
| | ADD: 477 S ROSEMARY SUITE # 169 |
| | CONT: CRAFT CONSTRUCTION |
| | TEL: (561)275-8770 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | OCT 19/2012 |
| | ACTION: DENIED |
| | |
| | 1) NEED LETTER FROM CITY PLACE INDICATING AN APPROVED |
| | REVIEW OF ELEMENTS WITHIN THE TENANT BUILD OUT. |
| | |
| | 2)2ND REQUEST THIS BUILDING MEETS THE DEFINITION OF A |
| | THRESHOLD BUILDING AND WILL NEED TO PROVIDE (3) THREE |
| | COPIES OF ALL DOCUMENTS, 1 FIELD SET, 1 BUILDING |
| | DEPARTMENT OFFICE SET & 1 SET FOR THRESHOLD INSPECTOR. |
| | |
| | THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) " |
| | THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH |
| | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| | THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA |
| | AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS. |
| | |
| | 2A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A |
| | SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON |
| | A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL |
| | INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE |
| | STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE |
| | ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING |
| | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. |
| | THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO |
| | PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO |
| | THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR |
| | COMPLIANCE WITH THE PERMITTED DOCUMENTS. |
| | |
| | 2B) THRESHOLD INSPECTOR: |
| | WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES |
| | DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL |
| | INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA |
| | STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS |
| | CODE. |
| | CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR |
| | PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION |
| | BEFORE THE PERMIT MAY BE ISSUED. |
| | |
| | 2C) THRESHOLD BLDG, REQUIRED STATEMENT: |
| | W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING |
| | WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE |
| | ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| | LOCAL AUTHORITY IN |
| | ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE. |
| | |
| | 2D) NOTE: A SOFT-HOLD (REVIEWS WII CONTINUE, THE PERMIT |
| | WILL NOT BE ISSUED UNTIL THE FOLLOWING ITEMS ARE |
| | SUBMITTED TO KEN CONRAD) WILL BE PUT ON THIS PROJECT |
| | UNTIL THESE ITEMS ARE COMPLETED AS REQUESTED BY THE |
| | CHIEF BUILDING INSPECTOR KEN CONRAD: |
| | |
| | 2D)(1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| | HISTORY FOR THIS TYPE OF CONCRETE RESTORATION. |
| | THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN |
| | CONRAD: [email protected] |
| | |
| | 2D()2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A |
| | RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. |
| | THE RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | CONTACT KEN CONRAD |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] |
| | |
| | NOTE: 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES |
| | FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER |
| | HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE |
| | MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR |
| | WALLS AND CEILINGS. |
| | |
| | NOTE: PLEASE CALL THE CITY OF WEST PALM BEACH'S |
| | AUTOMATED TELEPHONE INSPECTIONS LINE (561) 805-6700) |
| | FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS. |
| | |
| | 3A)2ND REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS. |
| | THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE |
| | 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 3B) 2ND REQUEST. 2010 FBC 1609.1.2 PROTECTION OF |
| | OPENINGS. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE |
| | 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, |
| | |
| | 4) 2ND REQUEST. ARCHITECTURAL AND STRUCTURAL SHEETS ARE |
| | LACKING 2010 FBC-B 1609.1.1 DETERMINATION OF WIND |
| | DESIGN- CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | 4.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 4.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | |
| | 4.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 4.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 4.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE |
| | TABLE 1609.2(2) . |
| | |
| | 5) 2ND REQUEST. COMMENTS THAT DEAL WITH COMMENTS ON |
| | A100 DETAIL 03 AND 4S1 DETAILS 4,5 & 9 "STYROFOAM OR |
| | OTHER NON COMPRESSIBLE VOID FILLER CAPABLE OF |
| | SUPPORTING 150 PSF." |
| | |
| | 5A ) 2ND REQUEST. 2010 WEST PALM BEACH ADMINISTRATIVE |
| | CODE 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | SUCH INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL |
| | CODES SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR |
| | SHALL THE TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A |
| | SUBSTITUTE FOR SPECIFIC INFORMATION ... |
| | |
| | 5B) 2ND REQUEST. THE SPECIFIED PRODUCT STYROFOAM WILL |
| | NEED TO MEET THE REQUIREMENTS OF THE 2010 FBC SECTION |
| | 603.1. COMBUSTIBLE MATERIALS IN TYPE II CONSTRUCTION, |
| | (3) |
| | FOAM PLASTICS IN ACCORDANCE WITH CHAPTER 26, |
| | |
| | 5C) 2ND REQUEST. THE SPECIFIED PRODUCT STYROFOAM WILL |
| | NEED TO MEET THE REQUIREMENTS OF THE 2010 FBC SECTION |
| | 603.1. COMBUSTIBLE MATERIALS IN TYPE II CONSTRUCTION, |
| | (12) |
| | STAGES & PLATFORM CONSTRUCTION IN ACCORDANCE WITH 410.3 |
| | & 4, RESPECTIVELY. |
| | 2010 FBC-B 410.4 PLATFORM CONSTRUCTION. |
| | PERMANENT PLATFORMS SHALL BE CONSTRUCTED OF MATERIALS |
| | AS REQUIRED FOR THE TYPE OF CONSTRUCTION OF THE |
| | BUILDING IN WHICH THE PERMANENT PLATFORM IS LOCATED. |
| | PERMANENT PLATFORMS ARE PERMITTED TO BE CONSTRUCTED OF |
| | FIRE-RETARDANT-TREATED WOOD FOR TYPES I, II AND IV |
| | CONSTRUCTION WHERE THE PLATFORMS ARE NOT MORE THAN 30 |
| | INCHES (762 MM) ABOVE THE MAIN FLOOR, AND NOT MORE THAN |
| | ONE-THIRD OF THE ROOM FLOOR AREA AND NOT MORE THAN |
| | 3,000 SQUARE FEET (279 M2) IN AREA. WHERE THE SPACE |
| | BENEATH THE PERMANENT PLATFORM IS USED FOR STORAGE OR |
| | ANY PURPOSE OTHER THAN EQUIPMENT, WIRING OR PLUMBING, |
| | THE FLOOR ASSEMBLY SHALL NOT BE LESS THAN 1-HOUR |
| | FIRE-RESISTANCE-RATED CONSTRUCTION. WHERE THE SPACE |
| | BENEATH THE PERMANENT PLATFORM IS USED ONLY FOR |
| | EQUIPMENT, WIRING OR PLUMBING, THE UNDERSIDE OF THE |
| | PERMANENT PLATFORM NEED NOT BE PROTECTED. |
| | |
| | 5D) 2ND REQUEST. A802 DETAIL 02 DOES NOT PROVIDE THE |
| | TYPE OF MATERIALS THE RAISED BOWLING ALLEY FLOOR FOR |
| | TYPE I OR TYPE II AS FAR AS COMBUSTIBLE STILL STAND. |
| | 603.1.1 AND SECTION 410.4 FOR PLATFORM CONSTRUCTION. |
| | |
| | 6)COMPLIED. SHEET A102 INDICATES THE USE OF STAIRS IN |
| | MANY AREAS, PLEASE REVIEW 2010 FBC-B 1028.11.3 TREAD |
| | AND CONTRASTING MARKING STRIPE. |
| | |
| | 7) 2ND REQUEST. PLANS ( A503 DETAIL 07) APPEAR TO HAVE |
| | A LIFT BUT NO PRODUCT INFORMATION HAS BEEN PROVIDED FOR |
| | THE LIFT, PLEASE SUBMIT THE MANUFACTURERS |
| | SPECIFICATIONS FOR LIFT. 2010 FBC-B 3001.6(F) LIFT. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |