| 2012-10-18 12:03:47 | 477 SOUTH ROSEMARY AVENUE - SUITE #169 |
| | PERMIT #12100295 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | GENERAL: THE PERMIT INFORMTION INDICATES THIS PROJECT |
| | IS FOR SUITE #169; HOWEVER, THE PLANS ALL INDICATE |
| | SUITE #100. PLEASE CLARIFY. |
| | |
| | GENERAL: FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE |
| | DURING DEMOLITION AND RENOVATION ACTIVITIES. IN THE |
| | EVENT A FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR |
| | MORE THAN 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING |
| | SHALL BE PLACED UNDER A FIRE WATCH. ALL FIRE WATCH |
| | REQUESTS MUST BE SUBMITTED IN WRITING (FAX: |
| | 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE |
| | MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY. |
| | |
| | GENERAL: ALL ASSEMBLY AREAS SHALL BE PROVIDED WITH |
| | PERMANENT SIGNAGE INDICATING "NO SMOKING BY ORDER OF |
| | THE FIRE MARSHAL." |
| | |
| | GENERAL: EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED |
| | SEATS SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED |
| | IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE |
| | ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF |
| | OCCUPANTS PERMITTED FOR EACH ROOM. |
| | |
| | GENERAL: CURTAINS, DRAPES AND OTHER LOOSELY HANGING |
| | FINISHINGS/DECORATIONS SHALL MEET THE FLAME PROPAGATION |
| | CRITERIA OF NFPA 701 (MATERIAL WILL SELF EXTINGUISH |
| | ONCE DIRECT FIRE FLAME HAS BEEN REMOVED). THE INTERIOR |
| | FINISH MATERIALS FOR WALLS AND CEILINGS SHALL MEET THE |
| | SMOKE DEVELOPMENT (0-450) AND FLAME SPREAD (76-200) |
| | REQUIREMENTS FOR CLASS C INTERIOR FINISHES PER NFPA |
| | 101. |
| | |
| | GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW |
| | EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE |
| | BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE |
| | ORDERED FROM WWW.KNOXBOX.COM. |
| | |
| | GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT |
| | DOORS WITH EXIT SIGNS. |
| | |
| | GENERAL: PROVIDE A CONTRASTING MARKING STRIPE ON EACH |
| | LEADING EDGE OF THE STAIRS SO AS TO MAKE IT READILY |
| | APPARENT THAT AN ELEVATION CHANGE EXITS ON THE SHORT |
| | RUN OF STAIRS. |
| | |
| | LIFE SAFETY SHEET 001: TO HELP SIMPLIFY THE OVERALL |
| | SCHEME, PLEASE INCLUDE THE FOLLOWING INFORMATION ON THE |
| | LIFE SAFETY PLAN: EXIT SIGN LOCATIONS (WITH INDICATING |
| | CHEVRONS), FIRE EXTINGUISHER LOCATIONS, TRAVEL |
| | DISTANCES, COMMON PATH OF TRAVEL, ETC. |
| | |
| | ELECTRICAL: INDICATE THE LOCATION OF THE FACP AND THE |
| | VOICE EVACUATION PANEL. |
| | |
| | ELECTRICAL: FIRE ALARM VOICE EVACUATION SYSTEM SHALL |
| | OVERRIDE THE DJ/MUSIC SYSTEM TO ENSURE FIRE ALARM |
| | MESSAGE IS INTELLIGIBLE. |
| | |
| | WESLEY JOLIN |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |
| | |