| Plan Review Notes For Permit 12100295 |
| Permit Number |
12100295 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-10-30 15:32:23 | 12100295 | | | 477 S. ROSEMARY AVENUE # 169 | | | RECREATION COMPLEX | | | | | | PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW | | | COMMENTS. | | | | | | PROVIDE A LIGHTING DENSITY CALCULATION SHOWING | | | COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE | | | REQUIREMENTS. FBC 13-415 ABC.5 | | | | | | SHEET E1: | | | NOTE G23: MULTIWIRE BRANCH CIRCUITS REQUIRE A MEANS | | | THAT WILL SIMULTANEOUSLY DISCONNECT ALL UNGROUNDED | | | CONDUCTORS. NEC 210.4 | | | | | | SHEET E3: | | | PROVIDE A STRUCTURAL SUPPORT DETAIL FOR LIGHT FIXTURES | | | AND LIGHTING ARRAYS WEIGHING MORE THAN 50 POUNDS. NEC | | | 410.36, 314.27 | | | | | | SHEET E6: | | | PROVIDE A DETAIL FOR THE CORD STRAIN RELIEF REQUIRED | | | FOR THE PINSITTER CORD. NEC 400.10 | | | INDICATE AND LABEL ON THE PLAN THE METHOD SELECTED TO | | | PROVIDE THE REQUIRED SAFE WORKING CLEARANCES AND | | | DEDICATED WORKING SPACE AT THE ELECTRICAL PANEL BOARDS. | | | NEC 110.26, 240.24 | | | VERIFY THE BOWLING MACHINES AND THE AV EQUIPMENT ARE | | | LISTED BY A NATIONALLY RECOGNIZED TESTING LABORATORY | | | (NRTL). NEC 110.3, 600.3 | | | | | | SHEET E 11: | | | PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL | | | DISCONNECTS AND FOR FLASH PROTECTION. NEC 110.22, | | | 110.16 | | | | | | NOTE: | | | SEPARATE PERMITS ARE REQUIRED FOR VOICE AND DATA AND | | | FIRE ALARM SYSTEMS | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | | | | | | | | | | | | | | | | |
|