| Plan Review Notes For Permit 12100270 |
| Permit Number |
12100270 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-10-10 17:48:23 | RE-ROOF BUILDING REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO | | | BE INSTALLED. NEED TO VERIFY COMPLIANCE WITH THE WIND | | | LOADS OF SEC. 1609 FBC. | | | | | | 2- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS | | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | | 12-0203.06 SUBMITTED TO MEET THE DESIGN PRESSURES OF | | | SEC. 1609 FBC. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|