| 2012-12-13 11:53:02 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | REVIEWED FOR COMPLIANCE WITH THE FOLLOWING: |
| | FBC 2010 |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. DUCT SIZES MISSING IN SEVERAL LOCATIONS ON THE |
| | PLANS. EXAMPLES: RETURN DUCT SERVING STORAGE ROOM 123 |
| | MECH ROOM 124; RETURN DUCT SERVING SOILED LAUNDRY ROOM |
| | 127. THESE ARE ONLY EXAMPLES. PLEASE CHECK ENTIRE PLAN |
| | AND PROVIDE ALL MISSING DUCT SIZES. FBC-M 603.1 |
| | |
| | 2. PG M201: UNABLE TO DETERMINE DRYER EXHAUST DUCT |
| | LENGTH ON PLAN. WHAT IS THE TOTAL DEVELOPED LENGTH OF |
| | ALL VERTICAL AND HORIZONTAL SECTIONS? DRYER EXHAUST |
| | DUCT SHALL NOT EXCEED 35 FEET UNLESS DRYER |
| | MANUFATURER'S INSTALLATION INSTRUCTIONS PROVIDE FOR |
| | LONGER DUCT INSTALLATION. FBC-M 504.6. |
| | |
| | 3. PG M202: PLEASE CLARIFY THE AIR BALANCE OVERALL. |
| | THERE APPEARS TO BE MANY AREAS IN WHICH SUPPLY AND |
| | RETURN ARE 100% EQUAL. IF 100% OF AIR IS BEING |
| | RETURNED, HOW IS THERE ENOUGH CAPACITY FOR THE SUPPLY |
| | TO PROVIDE THE REQUIRED QUANTITIES OF VENTILATION AIR |
| | FOR EACH HABITABLE SPACE PER FBC-M SECTION 403. |
| | |
| | 4. SHOW HOW THE CONDITIONED SPACE IS TO BE PRESSURIZED |
| | WITH RESPECT TO THE OUTDOORS (POST-CONSTRUCTION, NOT |
| | DURING CONTAMINATION PREVENTION STAGE) PER FBC-EC |
| | SECTION 503.2.10.6. |
| | |
| | 5. PG M400: DETAIL #5 SHOWS MIN. 1 INCH SUPPORT STRAPS |
| | FOR FLEXIBLE DUCTS. FLEXIBLE DUCT SUPPORTS ARE REQUIRED |
| | TO BE MIN. 1.5 INCHES WIDE PER FBC-M 603.10.3. |
| | |
| | 6. PG M400: PROVIDE WIND RESISTANT ATTACHMENT DETAIL |
| | FOR ROOF MOUNTED EQUIPMENT. A NOTE ON THE PLAN CALLING |
| | FOR CODE COMPLIANT INSTALLATION IS NOT SUFFICIENT. |
| | PROVIDE SUFFICIENT DETAIL TO ALLOW FOR A REVIEW OF THE |
| | ATTACHMENT METHOD PER FBC-M 301.12 AND FBC-B 106.1. |
| | |
| | 7. SHOW HOW FAN SHUT-DOWN BY SMOKE DETECTION IS TO BE |
| | PROVIDED PER FBC-M 606.1. DETAIL #5 ON PG M600 SHOWS |
| | DUCT SMOKE DETECTORS ON SUPPLY SIDE AND RETURN SIDE. IS |
| | THIS CORRECT? ALSO, DETAIL DOES NOT SHOW THE DUCT SMOKE |
| | DETECTORS INTERLOCKED WITH FIRE ALARM SYSTEM. SHOW |
| | COMPLIANCE WITH FBC-M 606.4.1. |
| | |