| 2012-10-19 10:18:29 | 5200 EAST AVENUE |
| | PERMIT #12100245 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | GENERAL |
| | ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO |
| | THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION |
| | DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING |
| | SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR |
| | AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL |
| | HAVE "NO SMOKING" SIGNS POSTED. |
| | |
| | WHERE SMOKING IS PERMITTED, SAFE RECEPTACLES FOR |
| | SMOKING MATERIALS SHALL BE PROVIDED. |
| | |
| | EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS |
| | SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A |
| | CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM. |
| | SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF |
| | OCCUPANTS PERMITTED FOR EACH ROOM. |
| | |
| | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| | WWW.KNOXBOX.COM. |
| | |
| | |
| | FIRE ALARM SYSTEM |
| | FIRE ALARM SYSTEM SHALL MONITOR FIRE SPRINKLER SYSTEM |
| | FLOW AND TAMPER SWITCHES. COORDINATE LOCATION OF THE |
| | DEVICES TO BE MONITORED. |
| | |
| | |
| | FIRE SPRINKLER SYSTEM |
| | FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED |
| | SUPERVISING STATION IN ACCORDANCE WITH NFPA 72. |
| | |
| | FIRE SPRINKLER AREA OF OPERATION SHALL BE INCREASED BY |
| | 30% WHEN THE CEILING/ROOF PITCH EXCEEDS 2 IN 12. |
| | |
| | PER NFPA 24, BUILDINGS LESS THAN 40 FT IN HEIGHT, A |
| | BACKFLOW PREVENTER SHALL BE PERMITTED TO BE INSTALLED |
| | CLOSER THAN 40 FT BUT AT LEAST AS FAR FROM THE BUILDING |
| | AS THE HEIGHT OF THE WALL FACING THE BACKFLOW |
| | PREVENTER. |
| | |
| | INDICATE THE LOCATION OF THE NEAREST FIRE HYDRANT(S) |
| | AND THE PROPOSED LOCATION OF THE FIRE DEPARTMENT |
| | CONNECTION. FDC SHALL BE LOCATED WITHIN 150 FEET OF A |
| | HYDRANT AND BE READILY ACCESSIBLE TO THE FIRE |
| | DEPARTMENT. |
| | |
| | PROVIDE FIRE HYDRANT FLOW TEST DATA. |
| | |
| | |
| | KITCHEN |
| | THE MANUAL ACTIVATION DEVICE SHALL BE LOCATED ALONG THE |
| | EGRESS PATH AND BE A MINIMUM OF 10 FEET AND A MAXIMUM |
| | OF 20 FEET FROM THE KITCHEN EXHAUST SYSTEM. |
| | |
| | KITCHEN HOOD SUPPRESSION SYSTEM SHALL BE TIED INTO THE |
| | BUILDING FIRE ALARM SYSTEM TO INITIATE A GENERAL FIRE |
| | ALARM CONDITION. |
| | |
| | DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE |
| | HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE |
| | THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT |
| | TEMPERATURE REACHES 475F DEGREES AT 1-INCH BELOW THE |
| | SURFACE. |
| | |