| 2012-10-31 12:25:33 | BUILDING PLAN REVIEW |
| | PERMIT: 12100245 |
| | ADD: 5200 EAST AVE. |
| | CONT: KENNEDY CONTRACTORS, INC. |
| | TEL: (561)434-1300 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | OCT. 31/ 2012 |
| | ACTION: DENIED |
| | |
| | 1A) SHEET C2 & A-101 BOTH INDICATE THE EXISTING FINISH |
| | FLOOR ELEVATION AS 16.34' NAVD 88. THIS BUILDING IS |
| | LOCATED IN A AH FLOOD ZONE WITH A BASE FLOOD ELEVATION |
| | AT 17.00' NGVD. THE FLOOD INSURANCE RATE MAP (FIRM) IS |
| | USING TTHE NGVD 29 TERMINOLOGY AND ALL ELEVATIONS SHALL |
| | BE NGVD ON THE PLANS AS WELL AS FLOOD ELEVATION |
| | CERTIFICATES. PLEASE PROVIDE THE EXISTING SLAB |
| | ELEVATION FOR THIS STRUCTURE IN NGVD. PLEASE NOTE A |
| | ELEVATION OF 17.5 FT. NGVD IS REQUIRED BY CITY MUNI |
| | CODE 94-546 FOR RESIDENTIAL CONSTRUCTION. FOR |
| | COMMERCIAL PROJECTS THEY CAN BE FLOOD PROOFED PLEASE |
| | SEE CITY MUNI-CODE 94-546(2) . |
| | |
| | 1B) THIS SITE HAS MULTIPLE BUILDINGS UNDER ONE PCN |
| | NUMBER WITHOUT IDENTIFYING BUILDINGS IN REGARDS TO |
| | PERMITTING. PLEASE REVIEW CITY MUNI-CODE IN REGARDS TO |
| | SUBSTANIAL IMPROVEMENTS AND THE REQUIREMENTS FOR ALL |
| | NEW CONSTRUCTION AND SUBSTANTIAL IMPROVEMENTS SHALL BE |
| | ANCHORED TO PREVENT FLOTATION, COLLAPSE OR LATERAL |
| | MOVEMENT OF THE STRUCTURE, AND SHALL BE CONSTRUCTED |
| | WITH MATERIALS AND UTILITY EQUIPMENT RESISTANT TO FLOOD |
| | DAMAGE BY METHODS AND PRACTICES THAT MINIMIZE FLOOD |
| | DAMAGE. |
| | |
| | 2) 1/03/2013 COMPLIED. E-MAIL SENT FROM ENGINEER |
| | PROVIDING LOCATION FOR WIND DESIGN CRITERIA, S3 & S3.1. |
| | |
| | NEITHER THE ARCHITECTURAL SHEETS NOR STUCTURAL SHEETS |
| | PROVIDE PRESSURES FOR COMPONENTS & CLADDING TO THE 2010 |
| | FBC-B V-ULT. PLEASE PROVIDE THE WIND DESIGN CRITERIA TO |
| | 2010 FBC FOR BUILDING CATEGORY III. |
| | 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | 2.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 2.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | |
| | 2.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 2.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 2.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE |
| | TABLE 1609.2(2) .ROOF ZONES 1,2 & 3 FOR FLAT AND SLOPED |
| | ROOFS WALL ZONE 4 &5. |
| | |
| | 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 4) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 |
| | NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) STOREFRONTS, CURTAIN WALLS, WALL LOUVERS |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES INCLUDING ROOFING |
| | INSULATION |
| | (G) PRE-ENGINEERED A/C STANDS, A/C CURBING |
| | |
| | 5) 2010 ENERGY CODE 402.3 FENESTRATION 402.3.2 PLEASE |
| | PROVIDE SHGC FOR WINDOWS. |
| | |
| | 6) MISSING SOILS REPORT DATED 9/17/12 BY ARDAMON & |
| | ASSOCIATES. |
| | |
| | 7) PLEASE SEE DETAIL 12 /A-700 IS FOR OVER FLOW |
| | SCUPPERS PLEASE PROVIDE THE CALCULATIONS FOR SIZING OF |
| | ROOF SCUPPERS FOR ROOF AREA AND 1/2 OF PARAPET PER 2010 |
| | FBC-B 1503.4.2.1. |
| | |
| | 8) SHEET A-401 INDICATES THE USE OF RUHLON CEILING |
| | SYSTEM PLEASE PROVIDE MANUFACTURERS SPECIFICATIONS 2010 |
| | FBC-B 603.1. 7 INTERIOR FINISHESCEILING FINISHES |
| | IN ACCORDANCE WITH 801 & 803. |
| | |
| | 9) FOUNTAIN TO BE SUBMITTED UNDER SEPERATE PERMIT |
| | APPLICATION, PULL FEES FOR SEPERATE REVIEW AND |
| | INSPECTIONS. |
| | |
| | 10) AWNINGS DEPICTED IN PLANS ALSO REQUIRE A SEPERATE |
| | PERMIT, PULL FEES FOR SEPERATE PERMIT, REVIEW AND |
| | INSPECTIONS. |
| | |
| | 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |