Plan Review Notes
Plan Review Notes For Permit 12100243
Permit Number 12100243
Review Stop B
Sequence Number 2
Notes
Date Text
2012-11-13 12:55:02****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 FBC 2010 RESIDENTIAL 301.1, RESISTANCE TO WIND LOADS:
  
 1. THE "SHUTTER CONNECTION MOUNTING TYPE" WAS LEFT
 BLANK. THIS SHOULD BE A CONNECTION TYPE C1 THROUGH C8,
 SEE ANCHOR CHARTS ON SHEET 4.
  
 2. EDGE DISTANCE CANNOT BE 4" FOR WOOD SUBSTRATE AS YOU
 WOULD NOT BE FASTENING INTO THE STRUCTURE.
  
 3. ANCHOR SPACING SHOULD BE ONE DIMENSION, DISTANCE
 (PATTERN) OF ANCHOR SPACING.
  
 4. IT IS ACCEPTABLE TO EXCEED CODE COMPLIANCE, BUT
 PLEASE BE ADVISED THAT MINIMUM WIND DESIGN REQUIREMENT
 IS +42.3/-56.6 FOR ZONE 5, 10 SF FOR A 25' HIGH
 STRUCTURE. IF NO OPENINGS ARE LOCATED IN ZONE 5, ZONE 4
 WORST CASE IS +42.3/-45.8. ON THE INSTALLATION
 SCHEDULE, YOU SPECIFY DESIGN PRESSURES AS +73.2/-81.6,
 PRODUCT APPROVAL IS FOR DESIGN PRESSURES LESS THAN
 -75PSF.
  
  