| Plan Review Notes For Permit 12100209 |
| Permit Number |
12100209 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-10-11 14:27:48 | 300 CLEMATIS STREET - SUITE #1 | | | PERMIT #12100209 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF | | | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE | | | 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA | | | AMENDMENTS. | | | | | | PER NFPA 101 SECTION 39.3.1.2 (EXISTING BUSINESS | | | OCCUPANCY), "FLOORS THAT ARE BELOW THE STREET FLOOR AND | | | ARE USED FOR STORAGE OR OTHER THAN A BUSINESS OCCUPANCY | | | SHALL HAVE NO UNPROTECTED OPENINGS TO BUSINESS | | | OCCUPANCY FLOORS. | | | | | | INDICATE THE LOCATION OF THE EXISTING SPRINKLERS SO | | | PROPER SPRINKLER COVERAGE CAN BE VERIFIED. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|