Plan Review Notes
Plan Review Notes For Permit 12100209
Permit Number 12100209
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2012-10-11 14:27:48300 CLEMATIS STREET - SUITE #1
 PERMIT #12100209
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 PER NFPA 101 SECTION 39.3.1.2 (EXISTING BUSINESS
 OCCUPANCY), "FLOORS THAT ARE BELOW THE STREET FLOOR AND
 ARE USED FOR STORAGE OR OTHER THAN A BUSINESS OCCUPANCY
 SHALL HAVE NO UNPROTECTED OPENINGS TO BUSINESS
 OCCUPANCY FLOORS.
  
 INDICATE THE LOCATION OF THE EXISTING SPRINKLERS SO
 PROPER SPRINKLER COVERAGE CAN BE VERIFIED.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  