2012-11-26 09:28:552010 FBC
  
 DENIED BY BUILDING
  
 1) THE EXPOSURE CATEGORY OF B SPECIFIED ON THE PLANS IS
 NOT CORRECT. FBCR 301.2.1.4.3 REQUIRES THE SURFACE
 ROUGHNESS B TO PREVAIL IN THE UPWIND DIRECTION FOR A
 DISTANCE OF AT LEAST 1500 FEET. THIS STRUCTURE IS
 WITHIN 800 FEET OF THE INTER-COASTAL WATERWAY,
 THEREFORE, IT IS EXPOSURE C. PLEASE CORRECT.
  
 2) THE COMPONENT AND CLADDING PRESSURES FOR THE WALL
 AREAS ON THE PLANS ARE FOR EXPOSURE B. PLEASE REVISE
 THE PRESSURES TO REFLECT EXPOSURE CATEGORY C AND A MEAN
 ROOF HEIGHT OF 20 FEET. FBCR 301.2.1
  
 3) PROVIDE STRUCTURAL DETAILS FOR THE WINDOW AND DOOR
 INFILL FRAMING ON THE PLANS. CITY AMENDMENTS 107.2.1
 (REPEAT COMMENT)
  