| Plan Review Notes For Permit 12100196 |
| Permit Number |
12100196 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-11-26 09:28:55 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE EXPOSURE CATEGORY OF B SPECIFIED ON THE PLANS IS | | | NOT CORRECT. FBCR 301.2.1.4.3 REQUIRES THE SURFACE | | | ROUGHNESS B TO PREVAIL IN THE UPWIND DIRECTION FOR A | | | DISTANCE OF AT LEAST 1500 FEET. THIS STRUCTURE IS | | | WITHIN 800 FEET OF THE INTER-COASTAL WATERWAY, | | | THEREFORE, IT IS EXPOSURE C. PLEASE CORRECT. | | | | | | 2) THE COMPONENT AND CLADDING PRESSURES FOR THE WALL | | | AREAS ON THE PLANS ARE FOR EXPOSURE B. PLEASE REVISE | | | THE PRESSURES TO REFLECT EXPOSURE CATEGORY C AND A MEAN | | | ROOF HEIGHT OF 20 FEET. FBCR 301.2.1 | | | | | | 3) PROVIDE STRUCTURAL DETAILS FOR THE WINDOW AND DOOR | | | INFILL FRAMING ON THE PLANS. CITY AMENDMENTS 107.2.1 | | | (REPEAT COMMENT) | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|