2012-11-07 11:08:142010 FBC
  
 PLUMBING DENIED
  
 1) THE FIRST FLOOR POWDER ROOM IS NOT SHOWN ON THE
 PLUMBING RISER DIAGRAM. FBCR P3101 & CITY AMENDMENT
 107.2.1
  
 2) THE WATER CLOSET FOR BATH NUMBER 1 ON THE SECOND
 FLOOR IS NOT SHOWN ON THE PLUMBING RISER DIAGRAM. FBCR
 P3101 & CITY AMENDMENT 107.2.1
  
 3) THE SHOWER AND LAVATORY HORIZONTAL BRANCH IS NOT
 VENTED PROPERLY. FBCR P3108.2.1 STATES THAT NOT MORE
 THAN ONE WET-VENTED FIXTURE IS ALLOWED TO DISCHARGE
 UPSTREAM OF THE DRY VENTED FIXTURE. PLEASE CORRECT.
  