| Plan Review Notes For Permit 12100196 |
| Permit Number |
12100196 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-11-07 11:08:14 | 2010 FBC | | | | | | PLUMBING DENIED | | | | | | 1) THE FIRST FLOOR POWDER ROOM IS NOT SHOWN ON THE | | | PLUMBING RISER DIAGRAM. FBCR P3101 & CITY AMENDMENT | | | 107.2.1 | | | | | | 2) THE WATER CLOSET FOR BATH NUMBER 1 ON THE SECOND | | | FLOOR IS NOT SHOWN ON THE PLUMBING RISER DIAGRAM. FBCR | | | P3101 & CITY AMENDMENT 107.2.1 | | | | | | 3) THE SHOWER AND LAVATORY HORIZONTAL BRANCH IS NOT | | | VENTED PROPERLY. FBCR P3108.2.1 STATES THAT NOT MORE | | | THAN ONE WET-VENTED FIXTURE IS ALLOWED TO DISCHARGE | | | UPSTREAM OF THE DRY VENTED FIXTURE. PLEASE CORRECT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|