| Plan Review Notes For Permit 12100196 |
| Permit Number |
12100196 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-11-07 11:30:14 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) CITY AMENDMENTS 107.2.1 REQUIRES ALL INFORMATION, | | | DRAWINGS, SPECIFICATIONS AND ACCOMPANYING DATA TO BEAR | | | THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR | | | THE DESIGN. PLEASE CORRECT. | | | | | | 2) SPECIFY THE WIND-SPEED DATA AND EXPOSURE CATEGORY ON | | | THE PLANS. FBCR 301.2.1 AND 301.2.1.4.3 | | | | | | 3) SPECIFY THE COMPONENT AND CLADDING PRESSURE FOR THE | | | WALL AREAS ON THE PLANS. FBCR 301.2.1 | | | | | | 4) PROVIDE STRUCTURAL DETAILS FOR THE WINDOW AND DOOR | | | INFILL FRAMING ON THE PLANS. CITY AMENDMENTS 107.2.1 | | | | | | 5) IN ORDER TO EXPEDITE PLAN REVIEW TIME WHEN | | | RESUBMITTING, PLEASE SUBMIT A RESPONSE LETTER | | | INDICATING HOW THE REVIEW COMMENTS HAVE BEEN ADDRESSED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|