| Plan Review Notes For Permit 12100172 |
| Permit Number |
12100172 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-10-16 09:15:37 | BUILDING PLAN REVIEW | | | PERMIT: 12100172 | | | ADD: 4400 PORTOFINO WAY | | | CONT: T. B.D. | | | TEL: (561)###-#### | | | 2010 FLORIDA BUILDING CODE W | | | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) NEW GATE ARMS: NO PRODUCT APPROVALS OR MANUFACTURERS | | | SPECS WERE SUBMITTED WILL NEED TO COMPLY WITH; | | | VEHICULAR GATE. A GATE THAT IS INTENDED FOR USE AT A | | | VEHICULAR ENTRANCE OR EXIT TO A FACILITY, BUILDING OR | | | PORTION THEREOF, AND THAT IS NOT INTENDED FOR USE BY | | | PEDESTRIAN TRAFFIC. | | | | | | 3110.3 VEHICULAR GATES INTENDED FOR AUTOMATION. | | | VEHICULAR GATES INTENDED FOR AUTOMATION SHALL BE | | | DESIGNED, CONSTRUCTED AND INSTALLED TO COMPLY WITH THE | | | REQUIREMENTS OF ASTM F 2200. | | | | | | 3110.4 VEHICULAR GATE OPENERS. | | | VEHICULAR GATE OPENERS, WHEN PROVIDED, SHALL BE LISTED | | | IN ACCORDANCE WITH UL 325. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | CONSTRUCTION SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | | | | | | | |
|