| Plan Review Notes For Permit 12100129 |
| Permit Number |
12100129 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-10-09 11:13:18 | 2047 PALM BEACH LAKES BOULEVARD | | | PERMIT #12100129 | | | MASTER #12030309 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | NONE OF THE ROOM HEAT OR SMOKE DETECTORS ARE SHOWN FROM | | | THE ENGINEERING CONSTRUCTION DOCUMENTS (SHEET E6). | | | | | | NO SUPERVISION IS PROVIDED FOR THE AUTOMATIC SPRINKLER | | | SYSTEM OR BACKFLOW PREVENTER. COORDINATE LOCATIONS OF | | | TAMPER AND FLOW SWITCHES. | | | | | | PROVIDE A MANUAL PULL STATION AT THE NURSE CONTROL | | | STATION. | | | | | | NO NOTIFICATION APPLIANCES PROVIDED IN PATIENT TOILET | | | #109, STAFF LOCKER #128, AND CORRIDOR #125 (OUTSIDE OF | | | OPERATING ROOM #119). | | | | | | NO NOTIFICATION APPLIANCES LOCATED IN THE OPERATING | | | ROOMS. INDICATE THE METHOD FOR ALERTING THE OCCUPANTS | | | OF A FIRE ALARM CONDITION. | | | | | | PER LOCAL AHJ POLICY, DUCT SMOKE DETECTORS SHALL | | | INITIATE A GENERAL FIRE ALARM CONDITION. | | | | | | A CERTIFICATE OF COMPLETION AND A THIRD PARTY | | | MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL | | | BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|