| Plan Review Notes For Permit 12100063 |
| Permit Number |
12100063 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-10-04 09:53:51 | 12100063 | | | 3215 S. FLAGLER DRIVE | | | LANDSCAPE LIGHTING | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION ON THE SITE | | | LIGHTING PLAN. | | | | | | PROVIDE NUMBER AND THE SIZE OF BRANCH CIRCUIT?S | | | INTENDED TO FEED THE SITE LIGHTING. NEC 240.4 | | | | | | INDICATE THE VOLTAGE, WIRING METHOD AND DEPTH OF ALL | | | CONDUCTORS. NEC 300.4, 411.3 | | | | | | INDICATE THE REQUIRED SAFE WIRING DISTANCE OF ALL | | | LIGHTING FIXTURES FROM THE NEAREST EDGE OF WATER FOR | | | POOLS, FOUNTAINS OR SIMILAR LOCATIONS. NEC 411.4(A) AND | | | (B) | | | | | | | | | ROBERT LECKY | | | ELECTRIC PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|