 3215 S. FLAGLER DRIVE
 LANDSCAPE LIGHTING
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION ON THE SITE
 LIGHTING PLAN.
  
 PROVIDE NUMBER AND THE SIZE OF BRANCH CIRCUIT?S
 INTENDED TO FEED THE SITE LIGHTING. NEC 240.4
  
 INDICATE THE VOLTAGE, WIRING METHOD AND DEPTH OF ALL
 CONDUCTORS. NEC 300.4, 411.3
  
 INDICATE THE REQUIRED SAFE WIRING DISTANCE OF ALL
 LIGHTING FIXTURES FROM THE NEAREST EDGE OF WATER FOR
 POOLS, FOUNTAINS OR SIMILAR LOCATIONS. NEC 411.4(A) AND
 (B)
  
  