| 2012-12-14 13:18:05 | *** NOTE: *** | | | | | | 1) PROVIDE MECHANICAL PLANS AND INFORMATION ASKED FOR | | | BELOW WHEN APPLYING FOR THE MECHANICAL PERMIT. | | | 1) SUBMIT COMPLETE COOLING LOAD CAL'S. NOT JUST A ONE | | | PAGE SUMMARY UNLESS IT IS SEALED AND SIGNED BY AN | | | ENGINEER. SEE 2010 FBC/ENERGY 403.6.1 EXCEPTION 2 AND | | | FBC/ R M1401.3. | | | 2) PROVIDE COMBUSTION AIR CAL'S. OR COMBUSTION AIR FOR | | | GAS CLOTHES DRYER IN THE UTILITY ROOM. PER 2010 FBC/R | | | G2407.1 | | | | | | MECHANICAL PLAN REVIEW BY: TOM GORDON (HY-BYRD INC.) | | | FOR ASSISTANCE CALL LUIS MARTINEZ (561) 805-6710 |
|