| Plan Review Notes For Permit 12100028 |
| Permit Number |
12100028 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-12-06 15:43:38 | *** CORRECTIONS NEEDED TO MECHANICAL PLANS *** | | | | | | 1) SUBMIT COMPLETE COOLING LOAD CAL'S. NOT JUST A ONE | | | PAGE SUMMARY UNLESS IT IS SEALED AND SIGNED BY AN | | | ENGINEER. SEE 2010 FBC/ENERGY 403.6.1 EXCEPTION 2 AND | | | FBC/ R M1401.3. | | | 2) PROVIDE COMBUSTION AIR CAL'S. OR COMBUSTION AIR FOR | | | GAS CLOTHES DRYER IN THE UTILITY ROOM. PER 2010 FBC/R | | | G2407.1 | | | | | | MECHANICAL PLAN REVIEW BY: TOM GORDON (HY-BYRD INC.) | | | FOR ASSISTANCE CALL LUIS MARTINEZ (561) 805-6710 |
|