| Date |
Text |
| 2012-11-02 16:14:44 | RESIDENTIAL (R3) ALTERATION/RENOVATION BUILDING REVIEW |
| | COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | 101.4.3 AND SEC. 103.2 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | 2- BEDROOM #1: FRONT WINDOW IS GOING TO BE ENCLOSED. |
| | SPECIFY SIZE OF EXISTING WINDOW TO BE ENCLOSED. EGRESS |
| | CAN'T BE REDUCED. SEC. 601.2 OF 2010 FBC-EXISTING |
| | BUILDING. PROVIDE WINDOW MANUFACTURER CUT SHEETS FOR |
| | OTHER WINDOW ON THIS BEDROOM TO DEMONSTRATE THAT THIS |
| | WINDOW WILL MEET THE EGRESS REQUIREMENTS OF SEC. R310 |
| | OF 2010 FBC-RESIDENTIAL. |
| | |
| | 3- SHEET 1.2: |
| | A) DESIGN PARAMETERS: (1) REVISE THE ROOF LIVE LOAD. |
| | SEE TABLE R301.6 OF 2010 FBC-RESIDENTIAL AND REVISE AS |
| | REQUIRED. (2) ALSO REVISE THE ROOF LIVE LOAD SHOWN ON |
| | STRUCTURAL NOTE #2(A). |
| | |
| | B) REVISE STRUCTURAL NOTE #2(C). DESIGN PARAMETERS |
| | SPECIFY EXPOSURE "D" NOT "B". REVISE AS REQUIRED TO |
| | MATCH. |
| | |
| | C) SPECIFY SAFETY GLASS AS REQUIRED BY SEC. R308.4 FOR |
| | EAST WINDOWS ON BOTH BEDROOMS. AND, FOR BATHROOM |
| | WINDOW. THIS APPLIES IF WINDOWS DON'T HAVE IMPACT |
| | GLASS. PRODUCT APPROVAL WAS NOT SUBMITTED. |
| | |
| | D) UTILITY AREA NEW OUTDOOR STEPS: (1) PROVIDE LANDING |
| | AS REQUIRED BY SEC. R311.3. (2) PROVIDE HANDRAILS AS |
| | REQUIRED BY SEC. R311.7.7. |
| | |
| | 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) ALL WINDOWS AS SHOWN ON PLANS. |
| | |
| | B) ALL EXTERIOR DOORS AS SHOWN ON PLANS. |
| | |
| | C) ALL WINDOW MULLIONS AS SHOWN ON PLANS. |
| | |
| | D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| | PLANS. PROVIDE ONLY THE PRODUCT APPROVAL COVER PAGE AND |
| | PAGE SHOWING THE CONNECTOR. |
| | |
| | E) STORM SHUTTERS IF WINDOWS AND DOORS DON'T HAVE |
| | IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE. |
| | |
| | 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS TO FBC. |
| | |
| | 6- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. SEC. 109.3 CITY AMENDMENTS TO FBC. UPDATE |
| | VALUATIONS AS REQUIRED. VA;LUATION TO INCLUDE ALL |
| | PROFESSIONAL DESIGN FEES, ALL LABOR AND MATERIALS AND |
| | CONTRACTOR'S OVERHEAD AND PROFIT. PROVIDE COPY OF |
| | SIGNED CONTRACT SIGNED BY OWNER AND CONTRACTOR. |
| | |
| | 7- SHEET 2.2: |
| | A) DESIGN PRESSURES FOR DOORS AND WINDOWS DON'T |
| | CORRESPOND TO EXPOSURE "D' AS SPECIFIED ON THE DESIGN |
| | CRITERIA ON SHEET 1.2. REVISE AS REQUIRED. SEC. 107.2.1 |
| | CITY AMENDMENTS TO FBC. |
| | |
| | B) TYPICAL WOOD FRAME DETAILS FOR WINDOWS, DOORS AND |
| | WALLS: (1) SPECIFY SIZE OF HEADERS. SEC. 107.2.1 CITY |
| | AMENDMENTS TO FBC. (2) BELOW THE WINDOW OPENINGS THERE |
| | IS A NOTE SAYING THAT NO CONNECTORS ARE REQUIRED. |
| | CLARIFY WHY NOT. SEC. 107.2.1 CITY AMENDMENTS TO FBC. |
| | |
| | 8- PROVIDE COMPLETE WALL SECTION SHOWING ALL FRAMING |
| | MEMBERS, CONNECTORS, INSULATION, WALL SHEATHING, DOUBLE |
| | VAPOR BARRIER, STUCCO THICKNESS, ETC. AS REQUIRED BY |
| | SEC. 107.3.5.3(5) CITY AMENDMENTS TO FBC. |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |