| 2012-11-27 09:59:56 | BUILDING PLAN REVIEW |
| | PERMIT: 12100015 |
| | ADD: 2316 S DIXIE HWY |
| | CONT: ARCA CONSTRUCTION |
| | TEL: (772)336-4296 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | PROVISO: |
| | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | 4A) 11/21/2012 I SPOKE WITH THE DESIGNER OF RECORD A |
| | CORRECTED WIND DESIGN CRITERIA WILL NEED TO BE |
| | SUBMITTED , PLEASE CALCULATE TO AT LEAST THE MINIMUM |
| | FOR OUR WIND SPEED ZONE OF 170 MPH VULT. |
| | 4B) KIOSK LETTER FOR FLOOR ANCHORING DOES NOT HAVE |
| | TYPED THE PERMIT NUMBER AND ADDRESS LOCATION, THESE ARE |
| | HAND WRITTEN IN, IT CAN BE TAKEN THIS IS A GENERIC |
| | LETTER, PLEASE INDICATE PERMIT AND LOCATION IN THE |
| | LETTER HEADING. |
| | 4C) ROY BROWN IS INDICATED ON THE PLANS AS THE ENGINEER |
| | OF RECORD, SHOP DRAWING STAMP FROM MR BROWN IS MISSING |
| | INDICATING THAT HE HAS REVIEWED AND ACCEPTEDED THESE |
| | DOCUMENTS. FL 61G-15-30.006 (3) THE DELEGATED ENGINEER |
| | SHALL FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO |
| | THE ENGINEER OF RECORD FOR REVIEW. |
| | |
| | |
| | 6) COMPLIED. |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |