| Plan Review Notes For Permit 12100013 |
| Permit Number |
12100013 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-11-05 08:50:23 | 2010 FBC | | | PLUMBING DENIED | | | | | | 1) THE PLUMBING RISER DIAGRAM ON SHEET A-4 SHOWS TWO | | | WASHING MACHINE BRANCH DRAINS & VENTS AND THE PLANS | | | INDICATE ONE CLOTHES WASHER. CITY AMENDMENTS 107.2.1 | | | PLEASE CORRECT. | | | | | | 2) THE PLUMBING RISER DIAGRAM DOES NOT SHOW THE BRANCH | | | DRAIN & VENT FOR THE KITCHEN SINK THAT IS SPECIFIED ON | | | THE PLANS. CITY AMENDMENTS 107.2.1 PLEASE CORRECT. | | | | | | 3) THE DRAIN TRAP AND TRAP ARM FOR THE WASHING MACHINE | | | IS REQUIRED TO BE 2" PER FBCR P3201.7 AND THE RISER | | | DIAGRAM HAS 1-1/2". PLEASE CORRECT. | | | | | | 4) CITY AMENDMENTS 107.2.1 REQUIRES ALL INFORMATION, | | | DRAWINGS, SPECIFICATIONS AND ACCOMPANYING DATA TO BEAR | | | THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR | | | THE DESIGN. PLEASE CORRECT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|