| Plan Review Notes For Permit 12100013 |
| Permit Number |
12100013 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-10-25 10:22:16 | PLANS DENIED | | | 1) REFER TO SECTION M1602.4 BALANCED RETURN AIR | | | 2010 FBC (R) | | | 2) PROVIDE DUCT SIZE, CAN SIZE AND CFM ON PLANS. | | | PER SECTION 107 FBC 2012 | | | 3) PROVIDE EQUIPMENT SCHEDULE ON THE PLANS | | | PER SECTION 107 FBC 2012 | | | 4) PROVIDE ENERGY CALCULATION WITH THE PLANS. | | | PER FLORIDA ENERGY CODE SECTION 403.6.1 EQUIPMENT | | | SIZING. | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] |
|