| Plan Review Notes For Permit 12100003 |
| Permit Number |
12100003 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-11-17 16:22:11 | 5329 GEORGIA AVENUE | | | PERMIT #12100003 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | REPEAT COMMENTS: | | | | | | NO OCCUPANCY TYPE HAS BEEN INDICATED ON THE PLANS SO | | | THE PLANS WILL BE TREATED AS SHELL SPACE ONLY. SEPARATE | | | PLANS AND PERMITS MAY BE NEEDED FOR OCCUPANCY BY | | | TENANTS. | | | | | | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | | | | PROVIDE EMERGENCY LIGHTS AND EXIT SIGNS. | | | | | | PROVIDE BUILDING ADDRESS WITH SUITE NUMBERS VISIBLE | | | FROM THE STREET. NUMBERS/LETTERS SHALL BE ATTACHED TO | | | THE BUILDING AND BE AT LEAST SIX-INCHES IN HEIGHT WITH | | | 1-INCH STROKE AND SHALL CONTRAST THE BACKGROUND. | | | | | | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH | | | EXIT SIGNS. | | | | | | EACH FIRE-RATED BARRIER SHALL BE PERMANENTLY IDENTIFIED | | | WITH SIGNS OR STENCILING READING FIRE/SMOKE | | | BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE AT | | | LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH. | | | IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON | | | CENTER. | | | | | | PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL | | | BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 |
|