Plan Review Notes
Plan Review Notes For Permit 12100003
Permit Number 12100003
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2012-11-17 16:22:115329 GEORGIA AVENUE
 PERMIT #12100003
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENTS:
  
 NO OCCUPANCY TYPE HAS BEEN INDICATED ON THE PLANS SO
 THE PLANS WILL BE TREATED AS SHELL SPACE ONLY. SEPARATE
 PLANS AND PERMITS MAY BE NEEDED FOR OCCUPANCY BY
 TENANTS.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 PROVIDE EMERGENCY LIGHTS AND EXIT SIGNS.
  
 PROVIDE BUILDING ADDRESS WITH SUITE NUMBERS VISIBLE
 FROM THE STREET. NUMBERS/LETTERS SHALL BE ATTACHED TO
 THE BUILDING AND BE AT LEAST SIX-INCHES IN HEIGHT WITH
 1-INCH STROKE AND SHALL CONTRAST THE BACKGROUND.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 EACH FIRE-RATED BARRIER SHALL BE PERMANENTLY IDENTIFIED
 WITH SIGNS OR STENCILING READING FIRE/SMOKE
 BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE AT
 LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH.
 IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON
 CENTER.
  
 PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL
 BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730