| 2012-10-04 13:56:18 | 2511 SOUTH DIXIE HIGHWAY | | | PERMIT #12090745 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | | | | NO ILLUMINATION PROVIDED FOR THE STORAGE ROOM. | | | | | | PROVIDE ILLUMINATED EXIT SIGNS AND PROVIDE TACTILE | | | SIGNAGE AT EXIT DOORS. | | | | | | ANY AREA (STORAGE) HAVING A DEGREE OF HAZARD GREATER | | | THAN NORMAL TO THE GENERAL OCCUPANCY (BUSINESS) OF THE | | | BUILDING, SHALL BE SEPARATED FROM NON-STORAGE AREAS | | | WITH A 1-HOUR FIRE-RATED BARRIER. DOORS SHALL BE SELF | | | CLOSING, POSITIVE LATCHING, AND FIRE-RATED FOR AT LEAST | | | 45-MINUTES PER SECTION 8.7 OF NFPA 101. | | | | | | PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET. | | | NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT | | | LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL | | | CONTRAST THE BACKGROUND | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|