| 2012-10-04 11:01:58 | BUILDING PLAN REVIEW |
| | PERMIT: 12090742 |
| | ADD: 1610 PALM BEACH LAKES BLVD |
| | CONT: DOSDOURIAM ENTERPRISES |
| | TEL: (561)644-4704 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | OCT. 04/ 2012 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A.04 INDICATES A NEW JM PVC SINGLE PLY ROOFING |
| | SYSTEM TO BE APPLIED OVER THE EXISTING ROOF. |
| | |
| | 1A) FLORIDA STATUTE 489.13(3)(G) NO GENERAL CONTRACTOR |
| | CERTIFIED AFTER 1973 SHALL ACT AS, HOLD HIMSELF OUT TO |
| | BE, OR ADVERTISE HIMSELF TO BE ROOFING CONTRACTOR |
| | UNLESS HE IS CERTIFIED OR REGISTERED AS A ROOFING |
| | CONTRACTOR. |
| | |
| | 1B) SHEET A.04 INDICATES A NEW JM PVC SINGLE PLY |
| | ROOFING SYSTEM TO BE APPLIED OVER THE EXISTING ROOF. |
| | PLEASE PROVIDE PRODUCT APPROVAL FOR SUCH APPLIACTION |
| | FOR GOING OVER AN EXISTING ROOF AND TYPE OF EXISTING |
| | ROOFING PRODUCT. REVIEW GENERAL LIMITATIONS TO SEE IF |
| | THE SYSTEM WILL ALLOW COVERING A EXISTING ROOF. |
| | |
| | 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(D) ROOFING PRODUCTS AND ASSEMBLIES |
| | |
| | 3) FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 4) 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 4.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 4.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | |
| | 4.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 4.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 4.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE |
| | TABLE 1609.2(2) . |
| | |
| | 5) A.04, PLANS DO NOT INDICATE TYPE OF CONSTRUCTION, |
| | TYPE I & TYPE II BUILDINGS 603.1 PLEASE SEE USE OF FOAM |
| | PRODUCTS 603.1 (3) FOAM PLASTICS IN ACCORDANCE WITH |
| | CHAPTER 26, 603.1(4) ROOF COVERINGS THAT HAVE AN A, B |
| | OR C CLASSIFICATION. |
| | |
| | 6) A.04 PLANS ALSO INDICATE THE USE OF PLYWOOD WITHIN |
| | THE ROOFDECK AREA, TYPE I, TYPE II BUILDINGS AND |
| | FIRERETARDENT TREATED WOOD AND WHERE IT CAN BE USED, |
| | PLEASE SEE 603.1(1.3) EXCEPTION. |
| | |
| | 7) A.04 DETAIL 3 INDICATES REMOVAL OF GUTTER SPILLWAY |
| | AND DETAIL # 2 NEW PIPING WITH A CUT SECTION 9/ A501.4 |
| | PAGE MISSING. THIS APPEARS TO BE A NEW COLUMN , THE |
| | BLOCK COLUMN ON THERIGHT HAND SIDE OF THE DETAIL FLOATS |
| | OUT IN MID AIR, HOW WILL THIS COLUMN BE SUPPORTED? |
| | 107.2.1.3, ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 8) THE UPPER PORTION OF DETAIL #2 INDICATES THE USE OF |
| | STEEL STUDS WITH EFIS FINISH YET NO PRODUCT APPROVALS |
| | WERE SUBMITTED FOR THIS PRODUCT THERE IS NO DETAIL HOW |
| | THIS COLUMN WILL BE FLASHED TO BE WEATHER TIGHT? |
| | |
| | 9) A.04 DETAIL # 3 INDICATES THE SLAB TO BE CORE |
| | DRILLED, THE PLANS INDICATE AN INTERIOR SPACE BELOW, |
| | BUT THERE IS NO NOTES ABOUT FIRE RATING OF THE FLOOR |
| | SLAB, TYPE OF MATERIAL TO BE USED IN RATING THE FLOOR |
| | SLAB, TABLE 601 FLOOR CONSTRUCTION RATING OF SLAB. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |