| 2012-10-04 10:26:03 | BUILDING APPROVED WITH EXCEPTION! | | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO | | | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO | | | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE | | | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE | | | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. | | | | | | DORM #4 & 8 BOTH INDICATE FLOOR TO BE CORED, PLANS ARE | | | DEFICIENT IN HOW THE FLOOR PENETRATION WILL COMPLY WITH | | | 2010 FBC-B 712.5 HORIZONTAL PENETRATIONS, & SECTION | | | 713.4. HORIZONTAL ASSEMBLIES. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | CONSTRUCTION SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
|