| 2012-11-08 11:00:48 | BUILDING PLAN REVIEW |
| | PERMIT: 12090707 |
| | ADD: 3401 PARKER AVE |
| | CONT: BIG D PAVING |
| | TEL: (561)697-2443 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | NOV. 08/ 2012 |
| | ACTION: DENIED |
| | |
| | COMMENT COMMON TO BOTH SHEETS T7.1 & T7.2R |
| | 1) 2ND REVIEW. BOTH SHEETS INDICATE UNDER GENERAL NOTE |
| | # 4 " THIS FABRIC SYSTEM IS DESIGNED TO RELEASE WHEN |
| | THE WIND SPEEDS EXCEED 90 MPH AND REFRENECE THE |
| | STRUCTURE IS DESIGNED TO 3105.4. UNDER THE 2010 FBC-B |
| | SECTION 3105.4 THERE IS NO RELEASE SYSTEM AT 90 MPH. |
| | PLEASE REVIEW SECTION: |
| | 2010 FBC-B 3105.4.2.1 FOR QUICK REMOVAL OR BREAK AWAY |
| | MEMBRANE OR FABRIC. BREAK AWAY SHOULD READ AT 75 MPH. |
| | 3105.4.2.2 FOR PERMANENT OR NONREMOVABLE FABRIC OR |
| | MEMBRANE. |
| | |
| | 2) 2ND REVIEW. UNDER THE NOTE TO OWNER IT INDICATES |
| | REMOVAL OF FABRIC WHEN WIND SPEEDS ARE EXSPECTED TO |
| | EXCEED 80 MPH ON T7.1 AND 90 MPH ON SHEET T7.2, T7.3 IN |
| | EXCESS OF 80 MPHAND T7.3R NOTE # 3 & 5 INEXCESS OF 90 |
| | MPH. PLEASE REVIEW SECTION 2010 FBC-B 3105.5.3 |
| | STRUCTURES DESIGNED TO BE READILY REMOVED OR |
| | REPOSITIONED DURING PERIODS OF HIGH WIND VELOCITY SHALL |
| | BE POSTED WITH A LEGIBLE AND READILY VISIBLE DECAL OR |
| | PAINTED INSTRUCTIONS TO THE OWNER OR TENANT TO REMOVE |
| | OR REPOSITION THE STRUCTURE OR PART THEREOF DURING SUCH |
| | PERIODS OF TIME AS ARE DESIGNATED BY THE U.S. WEATHER |
| | BUREAU AS BEING A HURRICANE WARNING OR ALERT. |
| | |
| | 3) 2ND REQUEST. UNDER THTE HEADING FABRIC THERE IS NO |
| | MENTION TO THE FIRE RESISTANCE REQUIREMENTS FOUND |
| | UNDER: |
| | 2010 FBC-B 3105.3.1 |
| | FABRIC USED FOR AWNINGS OR FABRIC-COVERED FRAMES SHALL |
| | MEET THE FLAME PROPAGATION PERFORMANCE CRITERIA OF NFPA |
| | 701. FLAME SPREAD OF 25 OR LESS IN ACCORDANCE WITH ASTM |
| | E-84. |
| | |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |