| 2012-12-14 13:28:44 | 854 CONNISTON ROAD | | | PERMIT #12090675 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | *****PROVISO***** | | | | | | NEW COMMENT: FIRE SPRINKLER - FLOWING HYDRAULIC NODES | | | #10, #15, #20, AND #25 HAVE A SPRINKLER OPERATING | | | PRESSURE LESS THAN 7 PSI. REVISE HYDRAULIC | | | CALCULATIONS. | | | | | | FIRE SPRINKLER: PROVIDE FIRE HYDRANT FLOW TEST | | | INFORMATION. A HYDRANT SHALL BE LOCATED WITHIN 150 FEET | | | OF THE FIRE DEPARTMENT CONNECTION. A PRIVATE FIRE | | | HYDRANT MAY NEED TO BE ADDED ON SITE TO ACCOMODATE THE | | | FDC. | | | | | | GUARDS, AT LEAST 42-INCHES TALL, SHALL BE PROVIDED AT | | | THE OPEN SIDES OF MEANS OF EGRESS (STAIRS, MEZZANINE, | | | ETC.) THAT EXCEED 30-INCHES ABOVE THE FLOOR. OPEN | | | GUARDS SHALL PROHIBIT THE PASSAGE OF A 4-INCH DIAMETER | | | SPHERE UP TO A HEIGHT OF 34-INCHES. THE TRIANGULAR | | | OPENINGS FORMED BY THE RISER, TREAD AND BOTTOM ELEMENT | | | OF THE GUARDRAIL SHALL PROHIBIT THE PASSAGE OF A 6-INCH | | | DIAMETER SPHERE. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 |
|