| Plan Review Notes For Permit 12090675 |
| Permit Number |
12090675 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-11-17 16:30:28 | 854 CONNISTON ROAD | | | PERMIT #12090675 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | *****PROVISO***** | | | | | | GUARDS, AT LEAST 42-INCHES TALL, SHALL BE PROVIDED AT | | | THE OPEN SIDES OF MEANS OF EGRESS (STAIRS, MEZZANINE, | | | ETC.) THAT EXCEED 30-INCHES ABOVE THE FLOOR. OPEN | | | GUARDS SHALL PROHIBIT THE PASSAGE OF A 4-INCH DIAMETER | | | SPHERE UP TO A HEIGHT OF 34-INCHES. THE TRIANGULAR | | | OPENINGS FORMED BY THE RISER, TREAD AND BOTTOM ELEMENT | | | OF THE GUARDRAIL SHALL PROHIBIT THE PASSAGE OF A 6-INCH | | | DIAMETER SPHERE. | | | | | | FIRE SPRINKLER: THE HYDRAULIC AREA SHALL BE INCREASED | | | BY 30% WHEN THE CEILING/ROOF PITCH EXCEEDS 2 IN 12 PER | | | NFPA 13 SECTION 11.2.3.2.4. | | | | | | FIRE SPRINKLER: PROVIDE FIRE HYDRANT FLOW TEST | | | INFORMATION. A HYDRANT SHALL BE LOCATED WITHIN 150 FEET | | | OF THE FIRE DEPARTMENT CONNECTION. A PRIVATE FIRE | | | HYDRANT MAY NEED TO BE ADDED ON SITE TO ACCOMODATE THE | | | FDC. | | | | | | FIRE SPRINKLER: AN UNNECESSARY CONTROL VALVE IS LOCATED | | | DOWNSTREAM OF THE FIRE DEPARTMENT CONNECTION. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 |
|