| Plan Review Notes For Permit 12090675 |
| Permit Number |
12090675 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-10-01 13:01:32 | PLANS DENIED | | | 1) PROVIDE RATED WALLS ON THE MECHANICAL PLANS | | | SECTION 107.2 CONSTRUCTION DOCUMENTS 2010 FBC | | | 2) PROVIDE PRODUCT APPROVALS ON OUTDOOR LOUVERS | | | AND WALL CAPS PER SECTION 107.3.4.1 GENERAL 2010 FBC | | | 3) CONDENSING UNIT MOUNT DETAIL ON PAGE M-2 SAY | | | 160 WIND LOAD NEED 170 WIND LOAD PER FIGURE | | | 1609A STRUCTURAL DESIGN 2010 FBC. | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] |
|