| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF |
| | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE |
| | 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA |
| | AMENDMENTS. |
| | |
| | ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO |
| | THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION |
| | DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. ALL |
| | DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| | SMOKING" SIGNS POSTED. |
| | |
| | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| | WWW.KNOXBOX.COM. |
| | |
| | PROVIDE A LIFE SAFETY PLAN FOR THE ENTIRE FIRST AND |
| | SECOND FLOORS SHOWING ALL EXITS, OCCUPANCY TYPES, |
| | OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS, EMERGENCY |
| | LIGHTING, TRAVEL DISTANCES, COMMON PATH OF TRAVEL ETC. |
| | |
| | THE BUILDING IS FUNCTIONING AS A MULTIUSE OCCUPANCY. |
| | INDICATE IF THE BUILDING IS DESIGNED FOR MIXED USE |
| | (NON-SEPARATED) OR SEPARATED USE PER SECTION 6.1.14.2.1 |
| | OF NFPA 101 FLORIDA EDITION 2009. |
| | |
| | CONFIRM THE BUILDING ADDRESS IS VISIBLE FROM THE |
| | STREET. NUMBERS SHALL BE ATTACHED TO THE BUILDING AND |
| | BE AT LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND |
| | SHALL CONTRAST THE BACKGROUND. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | CONFIRM ALL EXIT DOORS TO BE EQUIPPED WITH PANIC |
| | HARDWARE. NO OTHER LOCKS OR LATCHES NOT RELEASED BY THE |
| | PANIC HARDWARE WILL BE PERMITTED. |
| | |
| | GUARDS, AT LEAST 42-INCHES TALL, SHALL BE PROVIDED AT |
| | THE OPEN SIDES OF MEANS OF EGRESS (STAIRS, MEZZANINE, |
| | ETC.) THAT EXCEED 30-INCHES ABOVE THE FLOOR. OPEN |
| | GUARDS SHALL PROHIBIT THE PASSAGE OF A 4-INCH DIAMETER |
| | SPHERE UP TO A HEIGHT OF 34-INCHES. THE TRIANGULAR |
| | OPENINGS FORMED BY THE RISER, TREAD AND BOTTOM ELEMENT |
| | OF THE GUARDRAIL SHALL PROHIBIT THE PASSAGE OF A 6-INCH |
| | DIAMETER SPHERE. |
| | |
| | FIRE ALARM: CONFIRM FIRE ALARM SYSTEM WILL BE FULLY |
| | ADDRESSABLE. |
| | |
| | FIRE ALARM: PER LOCAL AHJ POLICY, DUCT SMOKE DETECTORS |
| | SHALL INITIATE A GENERAL FIRE ALARM CONDITION. |
| | |
| | FIRE SPRINKLER: THE HYDRAULIC AREA SHALL BE INCREASED |
| | BY 30% WHEN THE CEILING/ROOF PITCH EXCEEDS 2 IN 12 PER |
| | NFPA 13 SECTION 11.2.3.2.4. |
| | |
| | FIRE SPRINKLER: PROVIDE FIRE HYDRANT FLOW TEST |
| | INFORMATION. A HYDRANT SHALL BE LOCATED WITHIN 150 FEET |
| | OF THE FIRE DEPARTMENT CONNECTION. A PRIVATE FIRE |
| | HYDRANT MAY NEED TO BE ADDED ON SITE TO ACCOMODATE THE |
| | FDC. |
| | |
| | FIRE SPRINKLER: AN UNNECESSARY CONTROL VALVE IS LOCATED |
| | DOWNSTREAM OF THE FIRE DEPARTMENT CONNECTION. |
| | |