2012-10-04 12:05:34854 CONNISTON ROAD
 PERMIT #12090675
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. ALL
 DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE A LIFE SAFETY PLAN FOR THE ENTIRE FIRST AND
 SECOND FLOORS SHOWING ALL EXITS, OCCUPANCY TYPES,
 OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS, EMERGENCY
 LIGHTING, TRAVEL DISTANCES, COMMON PATH OF TRAVEL ETC.
  
 THE BUILDING IS FUNCTIONING AS A MULTIUSE OCCUPANCY.
 INDICATE IF THE BUILDING IS DESIGNED FOR MIXED USE
 (NON-SEPARATED) OR SEPARATED USE PER SECTION 6.1.14.2.1
 OF NFPA 101 FLORIDA EDITION 2009.
  
 CONFIRM THE BUILDING ADDRESS IS VISIBLE FROM THE
 STREET. NUMBERS SHALL BE ATTACHED TO THE BUILDING AND
 BE AT LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND
 SHALL CONTRAST THE BACKGROUND.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 CONFIRM ALL EXIT DOORS TO BE EQUIPPED WITH PANIC
 HARDWARE. NO OTHER LOCKS OR LATCHES NOT RELEASED BY THE
 PANIC HARDWARE WILL BE PERMITTED.
  
 GUARDS, AT LEAST 42-INCHES TALL, SHALL BE PROVIDED AT
 THE OPEN SIDES OF MEANS OF EGRESS (STAIRS, MEZZANINE,
 ETC.) THAT EXCEED 30-INCHES ABOVE THE FLOOR. OPEN
 GUARDS SHALL PROHIBIT THE PASSAGE OF A 4-INCH DIAMETER
 SPHERE UP TO A HEIGHT OF 34-INCHES. THE TRIANGULAR
 OPENINGS FORMED BY THE RISER, TREAD AND BOTTOM ELEMENT
 OF THE GUARDRAIL SHALL PROHIBIT THE PASSAGE OF A 6-INCH
 DIAMETER SPHERE.
  
 FIRE ALARM: CONFIRM FIRE ALARM SYSTEM WILL BE FULLY
 ADDRESSABLE.
  
 FIRE ALARM: PER LOCAL AHJ POLICY, DUCT SMOKE DETECTORS
 SHALL INITIATE A GENERAL FIRE ALARM CONDITION.
  
 FIRE SPRINKLER: THE HYDRAULIC AREA SHALL BE INCREASED
 BY 30% WHEN THE CEILING/ROOF PITCH EXCEEDS 2 IN 12 PER
 NFPA 13 SECTION 11.2.3.2.4.
  
 FIRE SPRINKLER: PROVIDE FIRE HYDRANT FLOW TEST
 INFORMATION. A HYDRANT SHALL BE LOCATED WITHIN 150 FEET
 OF THE FIRE DEPARTMENT CONNECTION. A PRIVATE FIRE
 HYDRANT MAY NEED TO BE ADDED ON SITE TO ACCOMODATE THE
 FDC.
  
 FIRE SPRINKLER: AN UNNECESSARY CONTROL VALVE IS LOCATED
 DOWNSTREAM OF THE FIRE DEPARTMENT CONNECTION.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  