| 2012-10-03 09:10:41 | 12090675 | | | 854 CONNISTON RD | | | CHURCH REMODEL | | | | | | THE FOLLOWING CODE REQUIREMENTS WERE NOTED ON THE PLAN. | | | | | | PROVIDE SAFETY LABELING FOR FLASH PROTECTION. NEC | | | 110.22, 110.16 | | | ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH | | | GFCI PROTECTION. NEC 422.52 | | | PROVIDE AN ENGINEERING DETAIL FOR THE LIGHT POLES AND | | | FIXTURES WHICH INDICATES CAPABILITY TO WITH STAND HIGH | | | WIND. PROVIDE AN EXPOSURE CATEGORY AND IMPORTANCE | | | FACTOR FOR THE DESIGN. FBC 1609, ASCE 7-10 | | | | | | NOTE: SEPARATE PERMITS ARE REQUIRED FOR LOW VOLTAGE | | | SYSTEMS, FIRE ALARM SYSTEMS AND SITE LIGHTING. | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|