2012-10-03 16:57:11BUILDING PLAN REVIEW
 PERMIT:12090675
 ADD: 854 CONNESTON RD
 CONT: TBD
 TEL: (786)663-6949
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 LAST KNOWN, LICENSED USE: DAYCARE
 1ST REVIEW
 OCT. 03/2012
 ACTION: DENIED
  
 1) MISSING INFORMATION MINIMUM PLAN REVIEW FOR
 COMMERCIAL BUILDINGS:
 2010 FBC/ WPB ADMINISTRATIVE CODE (CHAPTER 1)
 107.3.5.1.1.
 1A) (2) OCCUPANCY GEOUP
  
 1B) (3) MINIMUM BUILDING TYPE
  
 1C) (4) FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
  
 1D) (5)FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 EARLY WARNING SMOKE EVACUATION SYSTEMS
 SCHEMATIC FIRE SPRINKLERS
 PRE-ENGINEERED SYSTEMS
 RISER DIAGRAM
  
 1E) (6.) LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND
 SHALL INCLUDE THE FOLLOWING
 REQUIREMENTS:
 OCCUPANT LOAD AND EGRESS CAPACITIES
 EARLY WARNING
  
 1F) (7) OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL
 INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXITS
  
 1G) (8) 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE:
  
 WIND DESIGN CRITERIA REQUIREMENTS/ PRESSURES
  
 2) 2010 EXISTING BUILDING CODE 901.3 CHANGE OF
 OCCUPANCY CLASSIFICATION. WHERE THE OCCUPANCY
 CLASSIFICATION OF A BUILDING CHANGES, THE PROVISIONS OF
 SECTIONS 902 THROUGH 912 SHALL APPLY. THIS INCLUDES A
 CHANGE OF OCCUPANCY CLASSIFICATION WITHIN A GROUP AS
 WELL AS A CHANGE OF OCCUPANCY CLASSIFICATION FROM ONE
 GROUP TO A DIFFERENT GROUP
  
 2A) SHEET A1.02 INDICATES AN OCCUPANT LOAD OF 302 SEATS
 PLUS THE OCCUPANT LOAD OF THE STAGE (14) = 316
 OCCUPANTS. 2010 EXT BLD CODE SECTION 904.1
 FIRE PROTECTION REQUIREMENTS OF SECTION 912 SHALL APPLY
 WHERE A BUILDING OR PORTIONS THEREOF UNDERGO A CHANGE
 OF OCCUPANCY CLASSIFICATION.
 2010 EXT BLD CPDE 912.2 FIRE PROTECTION SYSTEMS.
  
 FIRE PROTECTION SYSTEMS SHALL BE PROVIDED IN ACCORDANCE
 WITH SECTIONS 912.2.1 AND 912.2.2.
  
 EXT BLD CODE 912.2.1 FIRE SPRINKLER SYSTEM.
  
 WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT
 REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE
 PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH
 CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH
 SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE
 CHANGE OF OCCUPANCY OCCURS.
 2010 FBC-BUILDING 903.2.1.1 GROUP A-1
 AN AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED FOR
 GROUP A-1 OCCUPANCIES WHERE ONE OF THE FOLLOWING
 CONDITIONS EXISTS:
 (2). THE FIRE AREA HAS AN OCCUPANT LOAD OF 300 OR MORE;
  
 2B) EXT BLD CODE 912.2.2 FIRE ALARM AND DETECTION
 SYSTEM.
 WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT
 REQUIRES A FIRE ALARM AND DETECTION SYSTEM TO BE
 PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH
 CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH
 SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE
 CHANGE OF OCCUPANCY OCCURS. EXISTING ALARM NOTIFICATION
 APPLIANCES SHALL BE AUTOMATICALLY ACTIVATED THROUGHOUT
 THE BUILDING. WHERE THE BUILDING IS NOT EQUIPPED WITH A
 FIRE ALARM SYSTEM, ALARM NOTIFICATION APPLIANCES SHALL
 BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF
 OCCUPANCY OCCURS AND SHALL BE AUTOMATICALLY ACTIVATED.
  
 3) SHEET A-1.02 THE WALL AND DOOR, DOOR 103, THAT
 SEPERATES THE SANCTUARY FROM THE BUSINESS AND CLASSROOM
 PORTION OF THE BUILDING DOES NOT APPEAR TO BE FIRE
 RATED. PLEASE REVIEW 303.1 EXCEPTION # 5, PLEASE
 PROVIDE THE SQUARE FOOTAGE OF THE BUSINESS AND
 CLASSROOMAND ASSOCIATED OCCUPANT LOADS, THIS WILL ALSO
 INCLUDE THE 2ND STORY PORTION OF THE CLASSROOM AREA
 THAT IS NOT PROVIDED.
  
 4) SHEET A-1.02 DOOR # 1.11 & S-1 INDICATE A NEW DOOR
 OPENING WITH PRESSURES, AS STATED ABOVE IN COMMENT (1G)
 PLEASE PROVIDE THE WIND DESIGN CRITERIA
 PER 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 4.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
 4.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
 4.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
 4.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
 4.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS
  
 7A) SHEET A-1.02 THE NEW FOYER LOBBY IS MISSING A CUT
 SECTION THROUGH THE NORTH SOUTH LOBBY WALLS ABOVE THE
 RESTROOMS. A4.01 INDICATES THESE WALLS CONTINUE TO THE
 UNDER SIDE OF THE ROOF SHEATHING BUT THE STUD SPACING
 IS NOT PROVIDED, NOR THE GAUGE OF THE STUD OR SPACING ,
 2010 FBC-B TABLE 2506.2 STEEL STUDS NON-LOAD BEARING,
 AND TYPE OF DRYWALL AND THICKNESS.
  
 7B) SHEET A-1.2 NOTE # 12 INDICATES THE USE OF A BILCO
 HATCH, PLEASE PROVIDE PRODUCT SPECS FOR HATCH PROVIDING
 CLEAR WIDTH AND LENGTH OF OPENING. THE 2010 FBC-M 306.2
 REQUIRES A CLEAR DOOR OPENING OF 36X80, THE EXCEPTION
 IS FOR A DWELLING UNIT AND LARGE ENOUGH FOR THE REMOVAL
 OF THE LARGEST APPLIANCE IN THE SPACE, A1 & A2 AIR
 HANDLIERS ARE 89X29X67 .
  
 8) THE ARCHITECTURAL PLANS DO NOT INDICATE WHAT TYPE OF
 FINISHES ARE GOING TO BE ON THE FOYER, HALLWAYS AND
 RESTROOM CEILING AS WELL AS WALLS WITHIN THE
 MECHANICAL ROOM, ADDITIONAL INFORMATION REQUIED.
 107.2.1.3.
  
 9) SHEET A3.01 NOTE 33 INDICATES NEW SHINGLE ROOF, WILL
 REQUIRE A SEPERATE PERMIT WITH ASSOCIATED REVIEWS AND
 FEES. PRODUCT APPROVALS WILL BE REQUIRED FOR
 SHINGLE ROOFING.
  
 10) PLEASE PROVIDE PLANS FOR THE 2ND STORY PORTION OF
 THIS FACILITY PROVIDE OCCUPANTCY, OCCUPANT LOADS,
 COMMON PATH OF TRAVEL AS WELL AS EGRESS STAIRS.
 MINIMUM CRITERIA FOR COMMERCIAL PLAN REVIEW
 107.3.5.1.1./ , CHANGE OF OCCUPANCY 2010 EXT BLDG CODE
 SECTION 9 12. NO PLANS WERE SUBMITTED.
  
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715