Plan Review Notes
Plan Review Notes For Permit 12090646
Permit Number 12090646
Review Stop B
Sequence Number 3
Notes
Date Text
2013-01-07 10:49:11BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- PROVIDE ENERGY CALCULATIONS FOR THE SEPARATE
 WORKSHOP/POOL CABANA BUILDING. SEC. 103.2.1 OF 2010
 FBC-ENERGY CONSERVATION.
 ***RESPONSE: SUBMITTED PACKAGE STATES THAT A/C
 INSTALLED FOR DEHUMIDIFICATION ONLY. THERE WAS AN
 EXCEPTION ON THE FBC 2007 FOR COMMERCIAL BUILDINGS
 ONLY. CURRENT CODE DON'T HAVE ANY EXEMPTIONS.
 THEREFORE, ENERGY CALCULATIONS ARE REQUIRED.
  
 2- A) REVISE ENERGY CALCULATIONS SUBMITTED FOR THE MAIN
 HOUSE. THE AREA-WEIGHTED AVERAGE MAXIMUM FENESTRATION
 SHGC PERMITTED SHALL BE 0.50. SEE SECTION 402.5 OF 2010
 FBC-ENERGY CONSERVATION. THIS IS REQUIRED BY SEC.
 405.2. ENERGY CALCULATIONS SUBMITTED SHOW 0.640. NEED
 TO REVISE.
  
 B) COORDINATE DOORS MATERIAL WITH PLANS AND PRODUCT
 APPROVALS SUBMITTED. THERE ARE NOT WOOD DOORS OR
 INSULATED WOOD FOR GUEST BEDROOM. SEE DOOR SCHEDULE.
 SEC. 405.5.3 OF 2010 FBC-ENERGY CONSERVATION.
  
 3-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ENTRY DOORS WITH SIZE (3'-6" X 8'-0") AND WITH
 SIDELITES AS SHOWN ON PLANS. AND TYPE OF DOOR (WOOD) AS
 SPECIFIED ON DOOR SCHEDULE. (NOT SUBMITTED)
  
 B) FLAT ROOF. AND, CLEARLY IDENTIFY WHICH APPROVED
 ASSEMBLY WILL BE INSTALLED. AND, PROVIDE SIGNED AND
 SEALED RAS 117 CALCULATIONS AS REQUIRED BY GENERAL
 LIMITATION #7 TO MEET THE DESIGN PRESSURES OF SEC.
 R301.2.1.4.3 FOR PERIMETER AND CORNER AREAS. (NOT
 SUBMITTED).
  
 C) WINDOW MULLION AND DOORS MULLIONS AS SHOWN ON PLANS.
 INCLUDING THE ONES FOR THE KITCHEN BAY WINDOW. AND,
 CLEARLY MARK ON DRAWINGS MULLION SIZE TO VERIFY DESIGN
 PRESSURES. SEC. R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL.
 (NOT SUBMITTED).
  
 D) TJI FLOOR SYSTEM SPECIFIED ON PLANS. NOA 00-1228.03
 SUBMITTED EXPIRED ON 08/14/2006.
  
 4- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) EACH AND ALL PRODUCT
 APPROVALS AS REQ'D BY SEC. 107.3.4.1 CITY AMENDMENTS TO
 FBC. PROVIDE REVIEW STAMP ON EACH PRODUCT APPROVAL
 COVER PAGE OR PROVIDE SIGNED AND SEALED LETTER CLEARLY
 IDENTIFYING EACH PRODUCT APPROVAL BY NUMBER AND
 SPECIFIC COMPONENT TO BE USED. GENERAL STATEMENT THAT
 ARCHITECT REVIEWED ALL PRODUCT APPROVALS IS NOT
 ACCEPTABLE.
  
 5- SPECIFY ATTIC ACCESS SIZE AND LOCATION FOR MAIN
 HOUSE. ATTIC ACCESS SHOWN INSIDE THE CLOSET OF THE
 GYMNASIUM ROOM IS NOT ALLOWED. REVISE LOCATION. AND,
 NEED ANOTHER ATTIC ACCESS TO ACCESS THE GUEST ROOM
 WING. ( ATTIC ACCESS WITH PULL DOWN STAIRS IS ONLY TO
 HAVE ACCESS TO THE ROOF DECK). SEC. R807.1.
  
 6- A) CLEARLY SPECIFY CRAWL SPACE VENTILATION SIZES.
 SIZE OF VENTS IS NOT SPECIFIED ON CRAWL SPACE NOTE ON
 SHEET S.1. SEC. R408. ALSO, PROVIDE COMPLETE
 INFORMATION FOR CRAWL SPACE FOR ACCESSORY STRUCTURE.
 SEE BUILDING SECTION ON SHEET A.5.
  
 B) REVISE LOCATION OF ACCESS TO THE CRAWL SPACE. SEC.
 R408.4. SHEET S.1: ONE OPENING LOCATED IN FRONT IS
 BLOCKED BY THE FRONT PORCH. THE OTHER OPENING IS
 BLOCKED BY THE A/C EQUIPMENT.
  
 7- PROVIDE YCENENE MANUFACTURER'S SPECIFICATION TO
 VERIFY COMPLIANCE WITH SEC. R316 AND R- VALUE SPECIFIED
 ON PLANS AND ENERGY CALCULATIONS. (NOT SUBMITTED).
  
 8- SHEET A.1: STEPS BETWEEN POOL AND OUTDOOR KITCHEN
 AREA. PROVIDE HANDRAILS AS REQ'D BY SEC. R311.7.7.
  
 9- SHEET S.2:
 A) PROVIDE COMPLETE ENGINEERED FLOOR PACKAGE. (1)
 SPECIFY BEAMS, LEDGERS AND ALL STRUCTURAL CONNECTORS.
 SEC. 107.2.1 CITY AMENDMENTS. (ONLY PARTIAL INFORMATION
 WAS PROVIDED).
  
 B) SPECIFY HOW PROTECTING THE WOOD AGAINST DECAY AS
 REQUIRED BY SEC. R317. (NOT ADDRESSED).
  
 C) MAIN HOUSE FRONT PORCH AND ACCESSORY STRUCTURE
 FLOORS: (1) SPECIFY SIZE OF JOISTS. (2) SPECIFY BEAMS
 SUPPORTING THE JOISTS. (3) SPECIFY ALL STRUCTURAL
 CONNECTORS FOR BEAMS AND JOISTS. (4) SPECIFY JOIST
 LEDGER SIZE AND FASTENERS. SEC. 107.2.1 CITY
 AMENDMENTS. (NOT ADDRESSED).
  
 D) PROVIDE COMPLETE FRAMING DETAILS FOR THE KITCHEN BAY
 WINDOW. WHERE IS BEAM B0?. SEC. 107.2.1 CITY
 AMENDMENTS. (NOT ADDRESSED).
  
 10- SHEET S-3:
 A) PROVIDE COMPLETE DETAILS/ SPECIFICATIONS FOR THE
 FRAMING OF THE BALCONIES. SPECIFY JOISTS SIZES AND
 CONNECTORS AT THE ENDS. SPECIFY BEAMS SIZES AND
 CONNECTORS. SEC. 107.2.1 CITY AMENDMENTS. (AND, HOW IS
 BALCONY FROM SANDY'S ROOM SUPPORTED?. IS IT
 CANTILEVERED?)
  
 B) ROOF TRUSSES; SPECIFY ALL BEAMS RECEIVING THE
 TRUSSES. SPECIFY ALL CONNECTORS FOR THE ROOF TRUSSES.
 SEC. 107.2.1 CITY AMENDMENTS. (NOT ADDRESSED).
  
 C) POOL CABANA/WORKSHOP: (1) SPECIFY ROOF JOISTS SIZE.
 (2) SPECIFY CONNECTORS. (3) SPECIFY LEDGER SIZE AND
 CONNECTORS. (4) SPECIFY BEAM FOR OVERHEAD DOOR. SEC.
 107.2.1 CITY AMENDMENTS. (NOT ADDRESSED).
  
 11- SHEET S.4:
 A) ROOF DECK; (1) SPECIFY JOIST SIZE AND STRUCTURAL
 CONNECTORS. (2) SPECIFY BEAMS AND LEDGERS AND
 STRUCTURAL CONNECTORS. (3) PROVIDE COMPLETE FRAMING
 DETAILS FOR ACCESS OPENING. SEC. 107.2.1 CITY
 AMENDMENTS. (NOT ADDRESSED).
  
 B) SHOW ALL BEAM SIZES ON THE BEAM SCHEDULE ON SHEET
 S.5. SEC. 107.2.1 CITY AMENDMENTS TO FBC. (NOT
 ADDRESSED).
  
 C) SPECIFY ALL CONNECTORS FOR THE ROOF TRUSSES. SEC.
 107.2.1 CITY AMENDMENTS. (NOT ADDRESSED).
  
 D) LOGGIA ROOF: SPECIFY LEDGER AND CONNECTORS FOR THE
 ROOF TRUSSES RESTING ON THE WALL. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC. (REPEAT COMMENT. AND SPECIFY ALL
 BEAMS).
  
 12- SHEET S-5:
 A) PROVIDE COMPLETE BEAM SCHEDULE. SEC. 107.2.1 CITY
 AMENDMENTS. (REPEAT COMMENT. COORDINATE WITH ITEMS 9,
 10 AND 11 ABOVE).
  
 B) PLYWOOD SHEATHING NAILING SCHEDULE: (1) REVISE
 NAILING SPACING FOR ROOF ZONE #1. NEED TO BE 6"O.C. NOT
 12"O.C. SEE SEC. R803.2.3.1.
  
 13- PROVIDE DETAILS/ SECTIONS AND SPECIFICATIONS
 SHOWING COMPLIANCE WITH SEC. R903.4 FOR THE ROOF
 DRAINAGE FROM THE ROOF DECK. ACCORDING TO EXTERIOR
 ELEVATIONS IT LOOKS LIKE ROOF DRAINS AND SECONDARY ROOF
 DRAINS ARE REQUIRED.
  