| Plan Review Notes For Permit 12090646 |
| Permit Number |
12090646 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-01-11 14:23:01 | *** PROVISO *** | | | 1) THE WORKSHOP MAY NOT BE AIR CONDITIONED FOR | | | DEHUMIDIFICATION UNLESS IT MEETS THE REQUIREMENTS OF | | | 2010 FBC/ENERGY 401.2, SUBMIT ENERGY CALCULATIONS. | | | | | | 2) A GAS UNDER COUNTER TANKLESS WATER HEATER CAN NOT BE | | | INSTALLED IN THE POOL CABANA BATHROOM, UNLESS IT MEETS | | | THE EXCEPTIONS OF 2010 FBC/R G2406.2. | | | | | | 3) THE BBQ GAS GRILL IN THE OUTDOOR KITCHEN WILL NEED A | | | OVERHEAD EXHAUST HOOD PER 2010 FBC/R 1505, UNLESS THE A | | | UNIT IS LISTED & LABELED FOR USE WITHOUT AN EXHAUST | | | HOOD AND MANUFACTURER'S INSTALLATION INSTRUCTIONS | | | SUPPORT THAT. | | | | | | 4) THE RETURN AIR MAY NOT PASS THROUGH THE PANTRY | | | (CLOSET) PER 2010 FBC/R M1602.2 (4). A DUCTED RETURN TO | | | THE KITCHEN WITH A SOLID DOOR AT THE PANTRY WOULD BE | | | LESS PROHIBITED UNDER THIS CIRCUMSTANCE. | | | | | | MECHANICAL PLAN REVIEW BY: | | | TOM GORDON (HY-BYRD INC.) (561) 805-6732 |
|