2012-10-11 11:32:3812090646
 220 ESSEX LANE
 NEW SFD
  
 PLEASE PROVIDE A RESPONSE TO THE FOLLOWING ELECTRICAL
 REVIEW COMMENTS.
  
 THE KITCHEN ISLAND COUNTER TOP REQUIRES A GFCI
 PROTECTED RECEPTACLE SERVED FROM A 20 AMPERE SMALL
 APPLIANCE CIRCUIT. NEC 210.52 (C) 2
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
 THE HALL WAY REQUIRES A RECEPTACLE. NEC 210.52 (H)
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 THE NEW BATHROOMS REQUIRES A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210.11 (C) (3)
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL
 GENERAL PURPOSE OUTLETS. NEC 210.12
 ADD RECEPTACLES SO THAT AT NO POINT ALONG THE FLOOR IN
 ANY WALL IS MORE THAN 6 FEET FROM A RECEPTACLE OUTLET
 AND AT WALL SPACES 2 FEET OR MORE IN WIDTH. (BEDROOM )
 NEC 210.52
 PROVIDE APPROPRIATELY SIZED FEEDER CONDUCTORS SIZES AND
 OVERCURRENT PROTECTION FOR THE ELECTRICAL SERVICE. NEC
 215.5, 220.40
 THE PANEL SCHEDULE IS INCOMPLETE. PROVIDE THE
 APPROPRIATE BRANCH CIRCUIT SIZES WITH OVERCURRENT
 PROTECTION (FOR BATHROOMS, KITCHENS, ETC.). NEC 210.52
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
  
 CALL OR EMAIL IF ADDITIONAL CLARIFICATION IS REQUIRED.
 THANK YOU.
  
  