| | 220 ESSEX LANE |
| | NEW SFD |
| | |
| | PLEASE PROVIDE A RESPONSE TO THE FOLLOWING ELECTRICAL |
| | REVIEW COMMENTS. |
| | |
| | THE KITCHEN ISLAND COUNTER TOP REQUIRES A GFCI |
| | PROTECTED RECEPTACLE SERVED FROM A 20 AMPERE SMALL |
| | APPLIANCE CIRCUIT. NEC 210.52 (C) 2 |
| | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO |
| | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND |
| | OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS |
| | APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON |
| | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH |
| | ROOM USED FOR SLEEPING. 2010 FBC R314, 315 |
| | THE HALL WAY REQUIRES A RECEPTACLE. NEC 210.52 (H) |
| | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 |
| | THE NEW BATHROOMS REQUIRES A DEDICATED 20 AMP BRANCH |
| | CIRCUIT. NEC 210.11 (C) (3) |
| | ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL |
| | GENERAL PURPOSE OUTLETS. NEC 210.12 |
| | ADD RECEPTACLES SO THAT AT NO POINT ALONG THE FLOOR IN |
| | ANY WALL IS MORE THAN 6 FEET FROM A RECEPTACLE OUTLET |
| | AND AT WALL SPACES 2 FEET OR MORE IN WIDTH. (BEDROOM ) |
| | NEC 210.52 |
| | PROVIDE APPROPRIATELY SIZED FEEDER CONDUCTORS SIZES AND |
| | OVERCURRENT PROTECTION FOR THE ELECTRICAL SERVICE. NEC |
| | 215.5, 220.40 |
| | THE PANEL SCHEDULE IS INCOMPLETE. PROVIDE THE |
| | APPROPRIATE BRANCH CIRCUIT SIZES WITH OVERCURRENT |
| | PROTECTION (FOR BATHROOMS, KITCHENS, ETC.). NEC 210.52 |
| | AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN |
| | SERVICE GROUND. NEC 250.94 |
| | |
| | CALL OR EMAIL IF ADDITIONAL CLARIFICATION IS REQUIRED. |
| | THANK YOU. |
| | |
| | |
| | ROBERT LECKY |
| | ELECTRIC PLANS EXAMINER |