Text |
| 2012-10-22 13:50:26 | RESIDENTIAL (R3) ADDITION/ALTERATION MECHANICAL REVIEW | | | COMMENTS. | | | CODE: 2010 FBC-RESIDENTIAL. | | | | | | 1- EQUIPMENT SIZE SHOWN ON THE A/C FLOOR PLAN DOESN'T | | | MATCH EQUIPMENT SIZE SHOWN ON THE EQUIPMENT SIZING | | | CALCULATIONS. REVISE AS REQUIRED TO MATCH. SEC. 403.6.1 | | | OF 2010 FBC-ENERGY CONSERVATION. | | | | | | 2- REVISE THE A/C AREA SHOWN ON THE EQUIPMENT SIZING | | | CALCULATIONS. SEE ARCHITECTURAL PLANS FOR CORRECT A/C | | | AREA. SEC. 107.2.1 CITY AMENDMENTS TO FBC. | | | | | | 3- SIZE OF WALL TRANSFER GRILL FOR THE BALANCED RETURN | | | AIR SHOWN ON THE MASTER BEDROOM IS TOO SMALL. IT | | | DOESN'T COMPLY WITH SEC. M1602.4 EXCEPTION #2. REVISE | | | AS REQUIRED. | | | | | | 4- DESIGNER RESPONSIBLE FOR THE PLANS TO PROVIDE NAME | | | AND SIGNATURE AS REQUIRED BY SEC. 107.2.1 CITY | | | AMENDMENTS TO FBC. | | | | | | 5- PLEASE CLARIFY WHY THE CFM'S SHOWN FOR THE LAUNDRY | | | (4 CFM), WALK IN CLOSET (3 CFM) AND BATH (6 CFM) ARE SO | | | LOW. SEC. 107.2.1 CITY AMENDMENTS TO FBC. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|