2012-10-22 13:50:26RESIDENTIAL (R3) ADDITION/ALTERATION MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC-RESIDENTIAL.
  
 1- EQUIPMENT SIZE SHOWN ON THE A/C FLOOR PLAN DOESN'T
 MATCH EQUIPMENT SIZE SHOWN ON THE EQUIPMENT SIZING
 CALCULATIONS. REVISE AS REQUIRED TO MATCH. SEC. 403.6.1
 OF 2010 FBC-ENERGY CONSERVATION.
  
 2- REVISE THE A/C AREA SHOWN ON THE EQUIPMENT SIZING
 CALCULATIONS. SEE ARCHITECTURAL PLANS FOR CORRECT A/C
 AREA. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 3- SIZE OF WALL TRANSFER GRILL FOR THE BALANCED RETURN
 AIR SHOWN ON THE MASTER BEDROOM IS TOO SMALL. IT
 DOESN'T COMPLY WITH SEC. M1602.4 EXCEPTION #2. REVISE
 AS REQUIRED.
  
 4- DESIGNER RESPONSIBLE FOR THE PLANS TO PROVIDE NAME
 AND SIGNATURE AS REQUIRED BY SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 5- PLEASE CLARIFY WHY THE CFM'S SHOWN FOR THE LAUNDRY
 (4 CFM), WALK IN CLOSET (3 CFM) AND BATH (6 CFM) ARE SO
 LOW. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  