| 2012-10-19 16:39:16 | RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW |
| | COMMENTS. |
| | CODE 2010 FBC-RESIDENTIAL. |
| | |
| | 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) |
| | TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED |
| | PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. |
| | REQUIRED BY COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED |
| | LAND DEVELOPMENT CODE. |
| | |
| | 2- BEDROOM #3: SPECIFY SAFETY GLASS FOR WINDOW ADJACENT |
| | TO THE CLOSET. SEC. R308.4(2). |
| | |
| | 3- SPECIFY ATTIC ACCESS LOCATION AND SIZE. SEC. R807.1 |
| | |
| | 4- A) PROVIDE COMPLETE MANUFACTURER SPECIFICATIONS FOR |
| | THE NEW FIREPLACE AND FIREPLACE FLUE AS SPECIFIED ON |
| | PLANS. DESIGNER OF RECORD TO REVIEW AND APPROVE IT |
| | PRIOR TO SUBMITTAL. SEC. 107.2.1 CITY AMENDMENTS TO |
| | FBC. |
| | |
| | B) PROVIDE MANUFACTURER SPECIFICATIONS SHOWING THAT THE |
| | CHIMNEY CAP AS SHOWN ON PLANS IS ALLOWED. SEC. 107.2.1 |
| | CITY AMENDMENTS TO FBC. |
| | |
| | 5- STORM SHUTTERS: PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE. AND, SPECIFY MOUNTING CONDITIONS (EX: WALL |
| | MOUNTED, BUILT OUT, ETC.) AND SPECIFIC ANCHOR TYPE AND |
| | SPACING TO BE USED TO VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES REQUIRED BY SEC. R301.2.1.4.3. |
| | |
| | 6- TITLE BLOCK NEEDS NAME OF PERSON SIGNING THE PLANS. |
| | SEC. 61G-16.004 FLORIDA ADMINISTRATIVE CODE. SEC. 107.1 |
| | CITY AMENDMENTS TO FBC. |
| | |
| | 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) STORM SHUTTERS. NEED PRODUCT APPROVAL FOR 2010 CODE |
| | VERSION. PRODUCT APPROVAL FL5351-R1 SUBMITTED IS NOT |
| | APPROVED. |
| | |
| | B) 70" HEIGHT CASEMENT WINDOWS AS SPECIFIED ON PLANS |
| | FOR KITCHEN WINDOW "B". MAXIMUM SIZE ALLOWED ON NOA |
| | 11-1114.20 SUBMITTED IS 63" HEIGHT. |
| | |
| | C) SELF ADHERING MODIFIED BITUMEN UNDERLAYMENT AS |
| | SPECIFIED ON TYPICAL WALL SECTION ON SHEET A3.0. |
| | PROVIDE PRODUCT APPROVAL THAT IS SUITABLE FOR SHINGLES |
| | INSTALLATION. |
| | |
| | 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS. SEC. |
| | 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 9-SOIL TEST REPORT NEEDS TO HAVE THE ENGINEER'S |
| | ORIGINAL SIGNATURE AND SEAL AS REQUIRED BY CHAPTER 471 |
| | FLORIDA STATUTE. SEC. 107.1 CITY AMENDMENTS. |
| | |
| | 10- ENERGY CALCULATIONS: |
| | A) REVISE THE A/C AREA. SEE FLOOR PLANS FOR CORRECT A/C |
| | AREA. SEC. 107.2.1 CITY AMENDMENTS TO FBC. |
| | B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| | INCLUDING THE BUILDER'S NAME. AND, REVISE THE |
| | JURISDICTION NUMBER. TIS IS 604700 NOT 604600. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | C) THE HEATING AND COOLING INFORMATION NEED TO MATCH |
| | INFORMATION SHOWN ON THE EQUIPMENT SIZING CALCULATIONS. |
| | REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS TO |
| | FBC. |
| | |