2012-10-02 11:24:377000 SOUTH DIXIE HIGHWAY
 PERMIT #12070800 - BUILDING "A" (WEST BLD.)
 PERMIT #12090630 - BUILDING "B" (EAST BLD.)
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REMOVE COOKING APPLIANCES FROM BUSINESS OCCUPANCY OR
 PROVIDE PROPER AUTOMATIC FIRE SUPPRESSION.
  
 ALL DEMOLITION/CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED.
  
 PROVIDE BUILDING ADDRESSES VISIBLE FROM THE STREET.
 NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT
 LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL
 CONTRAST THE BACKGROUND.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 STRUCTURES WITH LIGHT FRAME ROOF TRUSS CONSTRUCTION
 SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO THE
 BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE LETTER "R" DESIGNATION
 PER FLORIDA STATUTE 633.027 AND FLORIDA ADMINISTRATIVE
 CODE 69A-60.0081.
  