| Plan Review Notes For Permit 12090614 |
| Permit Number |
12090614 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-10-02 13:00:57 | 915 SOUTH DIXIE HIGHWAY | | | TRACKING #12090614 | | | PERMIT #12040368 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PERMIT #12040368 WAS ISSUED TO REOPEN PERMIT #11050010 | | | (REPLACE FACP PANEL AND POWER SUPPLY) VALUED AT $5565. | | | THE REVISED PLANS SHOW A LARGE INCREASE IN SCOPE OF | | | WORK WITH NO INCREASE IN JOB VALUE. PROVIDE REVISED JOB | | | VALUE. | | | | | | THE PLANS ARE REQUIRED TO BE SIGNED AND SEALED BY A | | | PROFESSIONAL ENGINEER NOT AN ARCHITECT. | | | | | | PROVIDE A FIRE ALARM RISER DIAGRAM. | | | | | | PROVIDE VOLTAGE DROP AND BATTERY CALCULATIONS. | | | | | | THE GROUND FLOOR DOES NOT INDICATE NOTIFICATION | | | APPLIANCES IN THE MEN'S AND WOMEN'S RESTROOM. | | | | | | THE SPACING OF THE NOTIFICATION APPLIANCES DO NOT | | | PROVIDE ADEQUATE COVERAGE PER NFPA 72. FOR EXAMPLE THE | | | HORN-STROBE DEVICES LOCATED ON THE MEZZANINE IN THE | | | CORRIDOR ARE SPACING ROUGHLY 100 FEET APART. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|