2012-10-18 17:06:35****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 FROM FIRST COMMENT LIST:
  
 1. OK.
  
 2. OK
  
 3. DOCUMENTS PREPARED BY AN ARCHITECT AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS
 FS481.
  
 A NEW FLOOR PLAN SUBMITTED, SIGNED BUT NOT SEALED. THE
 STRUCTURAL DETAIL PREVIOUSLY SUBMITTED FOR THE WINDOW
 FRAMING REPAIR IS NOT SIGNED AND SEALED.
  
 NEW COMMENT:
  
 4. ONLY ONE MULLION PRODUCT APPROVAL SUBMITTED. TWO
 REQUIRED, PLEASE SUBMIT.
  