2012-10-04 14:32:42****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. SCOPE NOT CLEAR. FIVE OPENINGS HIGHLIGHTED, ONE
 APPEARS TO BE EITHER SLIDING GLASS DOOR OR WINDOWS
 REQUIRING MULLIONS. REVISE PLAN SO SCOPE IS CLEAR, FBC
 106. IF MULLIONS ARE PROPOSED, PROVIDE PRODUCT
 APPROVAL.
  
 2. REVISE FLOOR PLAN TO INCLUDE WINDOW SIZES, WINDOW
 TYPE, ROOM DESIGNATIONS. NOTE EXISTING CONDITIONS (TYPE
 OF WINDOW) AND OPENING SIZE FOR BEDROOMS, FBC R310, FBC
 EB 604.1. THE CLEAR OPENING FOR BEDROOMS CANNOT BE
 REDUCED BY MORE THAN 5%.
  
 3. DOCUMENTS PREPARED BY AN ARCHITECT AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS
 FS481.
  