| Date |
Text |
| 2012-10-31 15:45:47 | RESIDENTIAL (R3) ALTERATION/RENOVATION BUILDING REVIEW |
| | COMMENTS. |
| | CODE: 2010 FBC |
| | |
| | 1- THIS HOUSE IS LOCATED ON FLOOD ZONE A5. TABLE |
| | R301.2(1) OF 2010 FBC-RESIDENTIAL AND SEC. 94-546 OF |
| | CITY CODE REQUIRES NEW CONSTRUCTION OR SUBSTANTIAL |
| | IMPROVEMENT SHALL HAVE THE LOWEST FLOOR ELEVATED 6 |
| | INCHES ABOVE THE BASE FLOOD ELEVATION. BASE FLOOD |
| | ELEVATIONS IS 7'-0". THEREFORE THE MIN. FINISH FLOOR |
| | ELEVATION IS 7'-6". PLEASE PROVIDE SURVEY SHOWING THE |
| | EXISTING FINISH FLOOR ELEVATION TO VERIFY COMPLIANCE. |
| | OTHERWISE, HOUSE MAY NEED TO BE RAISED TO COMPLY. |
| | ELEVATION CERTIFICATE IS REQUIRED ALSO. |
| | |
| | 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW BASED ON THE SCOPE OF WORK SHOWN ON PLANS. |
| | VALUATION TO INCLUDE ALL PROFESSIONAL FEES AND |
| | CONTRACTOR'S OVERHEAD AND PROFIT. PROVIDE COPY OF |
| | SIGNED CONTRACT. SEC. 109.3 CITY AMENDMENTS TO FBC. |
| | |
| | 3- ARCHITECT TO PROVIDE THE DESIGN PRESSURES REQUIRED |
| | BY SEC. R301.2.1.4.3 FOR THE NEW WINDOWS. NOTE: |
| | ACCORDING TO SEC. R301.2.1.4.3 THIS BUILDING IS LOCATED |
| | ON EXPOSURE "D". CONSIDER THIS WHEN CALCULATING THE |
| | DESIGN PRESSURES. |
| | |
| | 4- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT |
| | SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED |
| | BY SEC. 107.3.4.1 CITY AMENDMENTS TO FBC. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |
| 2012-10-30 10:43:28 | BUILDING REVIEW WAS LOCKED. OPENED A NEW STOP TO DO THE |
| | REVIEW. JG. |