| 2012-10-10 16:30:52 | 12090541 | | | 121 POTTER ROAD | | | SFD RENOVATION | | | | | | PLEASE PROVIDE THE FOLLOWING: | | | | | | THE KITCHEN ISLAND COUNTER TOP REQUIRES A GFCI | | | PROTECTED RECEPTACLE SERVED FROM A 20 AMPERE SMALL | | | APPLIANCE CIRCUIT. NEC 210.52 (C)2 | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND | | | OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS | | | APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON | | | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH | | | ROOM USED FOR SLEEPING. 2010 FBC R314, 315 | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | THE NEW BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH | | | CIRCUIT. NEC 210.11 (C) (3) | | | ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW | | | GENERAL PURPOSE OUTLETS. NEC 210.12 | | | | | | | | | ROBERT LECKY | | | ELECTRIC PLANS EXAMINER | | | [email protected] | | | | | | |
|