 121 POTTER ROAD
 SFD RENOVATION
  
 PLEASE PROVIDE THE FOLLOWING:
  
 THE KITCHEN ISLAND COUNTER TOP REQUIRES A GFCI
 PROTECTED RECEPTACLE SERVED FROM A 20 AMPERE SMALL
 APPLIANCE CIRCUIT. NEC 210.52 (C)2
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 THE NEW BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210.11 (C) (3)
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW
 GENERAL PURPOSE OUTLETS. NEC 210.12
  
  