| Plan Review Notes For Permit 12090535 |
| Permit Number |
12090535 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-09-24 14:01:49 | 12090535 | | | 2840 WILDERNESS ROAD | | | KITCHEN AND BATH REMODEL | | | | | | THE FOLLOWING CODE REQUIREMENTS WERE NOTED ON THE PLAN. | | | | | | PROVISO: | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND | | | OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS | | | APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON | | | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH | | | ROOM USED FOR SLEEPING. 2010 FBC R314, 315 | | | RECEPTACLES SERVICING KITCHEN COUNTERTOP SURFACES AND | | | BATH ROOMS REQUIRE GROUND FAULT PROTECTION. NEC 210.8 | | | | | | ROBERT LECKY | | | ELECTRIC PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|